AP112-1R7-2F1752
Circuit Breakers
CIRCUIT BREAKER
AP112-1R7-2F1752
Sensata Technologies Maryland Inc
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Body Length
1.500 inches maximum
-
Main Contact Tripping Mechanism Type
trip free
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
115.0 all locations
-
Arc Quenching Method
magnetic blowout
-
Switch Current Rating And Type In Amps
0.5 ac and 0.5 dc
-
Thread Series Designator
unef
-
Switch Voltage Rating And Type In Volts
120.0 ac and 50.0 dc
-
Auxiliary Switch Function And Quantity
1 alarm
-
Body Width
1.875 inches maximum
-
Terminal Type And Quantity
6 wire hook
-
Features Provided
high inrush protection
-
Bushing Length
0.380 inches maximum
-
Nonturn Device Length
0.130 inches nominal
-
Storage Type
general purpose warehouse
-
Trip Release Characteristic
time delay all locations
-
Center To Center Distance Between Terminals Parallel To Width
0.625 inches nominal
-
Actuator Function
trip-reset
-
Internal Trip Release Configuration
series trip all locations
-
Nonturn Device Diameter
0.140 inches nominal
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
500.0 dc all locations
-
Thread Pitch Diameters
+0.3503/+0.3537 inches
-
Operating Voltage Type And Rating Per Pole In Volts
50.0 dc all locations
-
Nominal Thread Size
0.375 inches
-
Thread Quantity Per Inch
32
-
Trip Release Method
magnetic-hydraulic all locations
-
Mounting Surface To Terminal End Distance
1.780 inches maximum
-
Actuator Position Designation
at pole two
-
Inclosure Protection Type For Which Designed
hermetically sealed
-
Switch Contact Arrangement
single pole, double throw
-
Center To Center Distance Between Terminals Parallel To Length
0.875 inches nominal
-
Nonturn Device Location
at 3 oclock and at 9 oclock
-
Body Style
multipole-single actuator type
-
Nonturn Device Radius
0.625 inches nominal
-
Case Material
metal
-
Manual Actuator Type And Quantity
1 toggle
-
Fragility Factor
moderately rugged
-
Maximum Continuous Load Current Rating Per Pole
17.5 amperes dc all locations
-
Switch Terminal Type
tab, solder lug
-
Special Handling Feature
magnetic
-
Pole Quantity
3
-
Circuit Protection Type
overcurrent all locations
-
Reset Method
manual
-
Mounting Facility Type And Quantity
1 threaded bushing w/panel seal
-
Switch Location And Position Designation
internal at pole three
-
Trip Delay Time In Seconds Per Rated Continuous Current
0.850 minimum at 200 pct all locations and 4.000 maximum at 200 pct all locations