AP14-1769-1
Circuit Breakers
CIRCUIT BREAKER
AP14-1769-1
Sensata Technologies Maryland Inc
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Main Contact Tripping Mechanism Type
trip free
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
115.0 all locations
-
Arc Quenching Method
magnetic blowout
-
Maximum Continuous Load Current Rating Per Pole
3.0 amperes ac all locations and 100.0 milliamperes dc all locations
-
Body Width
1.250 inches maximum
-
Frequency In Hertz
400.0 all locations
-
Thread Series Designator
unef
-
Operating Voltage Type And Rating Per Pole In Volts
240.0 ac all locations and 50.0 dc all locations
-
Nominal Thread Size
0.375 inches
-
Thread Quantity Per Inch
32
-
Trip Release Method
magnetic-hydraulic all locations
-
Mounting Facility Type And Quantity
1 threaded bushing
-
Mounting Surface To Terminal End Distance
1.780 inches maximum
-
Internal Trip Release Configuration
series trip first location
-
Inclosure Protection Type For Which Designed
hermetically sealed
-
Terminal Type And Quantity
4 wire hook
-
Center To Center Distance Between Terminals Parallel To Length
0.875 inches nominal
-
Body Style
multipole-single actuator type
-
Case Material
metal
-
Manual Actuator Type And Quantity
1 toggle
-
Body Length
1.500 inches maximum
-
Actuator Position Designation
between pole one and two
-
Circuit Protection Type
overcurrent all locations
-
Internal Trip Release Configuration
relay trip second location
-
Pole Quantity
2
-
Reset Method
manual
-
Unpackaged Unit Weight
2.100 ounces
-
Storage Type
general purpose warehouse
-
Center To Center Distance Between Terminals Parallel To Width
0.625 inches nominal
-
Actuator Function
trip-reset
-
Bushing Length
0.380 inches maximum
-
Trip Delay Time In Seconds Per Rated Continuous Current
0.009 minimum at 150 pct all locations and 0.005 minimum at 200 pct all locations and 0.050 maximum at 150 pct all locations and 0.017 maximum at 200 pct all locations
-
Trip Release Characteristic
instantaneous all locations and time delay all locations
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
300.0 ac all locations and 500.0 dc all locations