160-006-70
Circuit Breakers
CIRCUIT BREAKER
160-006-70
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Body Style
7a single pole type
-
Body Length
2.189 inches maximum
-
Body Width
0.750 inches maximum
-
Center To Center Distance Between Terminals Parallel To Length
1.438 inches nominal
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
0.181 inches nominal
-
Pole Quantity
1
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
6000.0 dc single location
-
Circuit Protection Type
overcurrent single location
-
Trip Release Method
thermal single location
-
Manual Actuator Type And Quantity
1 push-pull
-
Internal Trip Release Configuration
series trip single location
-
Nominal Thread Size
0.138 inches
-
Trip Release Ambient Temp Rating
-55.0 deg celsius minimum single location and 125.0 deg celsius maximum
-
Bushing Length
0.250 inches nominal
-
Mounting Surface To Terminal End Distance
2.250 inches maximum
-
Mounting Facility Type And Quantity
2 threaded hole
-
Thread Quantity Per Inch
32
-
Maximum Continuous Load Current Rating Per Pole
70.0 amperes dc single location
-
Operating Voltage Type And Rating Per Pole In Volts
30.0 dc single location
-
Trip Release Characteristic
time delay single location
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
138.0 single location
-
Ultimate Trip Time Per Pole In Seconds
3600.000 maximum single location
-
Reset Method
manual
-
Main Contact Tripping Mechanism Type
trip free
-
Actuator Function
trip-reset
-
Actuator Position Designation
at pole one
-
Trip Delay Time In Seconds Per Rated Continuous Current
25.000 minimum at 200 pct single location and 60.000 maximum at 200 pct and 2.000 minimum at 400 pct and 7.000 maximum at 400 pct
-
Thread Series Designator
unc
-
Terminal Type And Quantity