S371D957G09
Circuit Breakers
CIRCUIT BREAKER
S371D957G09
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Trip Release Method
thermal-magnetic all locations
-
Inclosure Protection Type For Which Designed
fungus resistant
-
Trip Delay Time In Seconds Per Rated Continuous Current
170.000 minimum at 200 pct all locations and 460.000 maximum at 200 pct all locations
-
Terminal Type And Quantity
4 compression
-
Overall Height
4.312 inches nominal
-
Manual Actuator Type And Quantity
1 toggle
-
Frequency In Hertz
60.0 all locations
-
Actuator Position Designation
between pole one and two
-
Main Contact Tripping Mechanism Type
trip free
-
Nominal Thread Size
0.164 inches
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
15000.0 ac all locations and 1000.0 dc all locations
-
Overall Width
5.500 inches nominal
-
Overall Length
10.125 inches nominal
-
Case Material
plastic
-
Body Style
rectangular dimensional envelope
-
Pole Quantity
2
-
Thread Series Designator
unc
-
Reset Method
manual
-
Maximum Continuous Load Current Rating Per Pole
225.0 amperes ac all locations and 225.0 amperes dc all locations
-
Trip Release Ambient Temp Rating
40.0 deg celsius nominal all locations
-
Trip Release Characteristic
time delay all locations
-
Actuator Function
trip-reset
-
Operating Voltage Type And Rating Per Pole In Volts
600.0 ac all locations and 250.0 dc all locations
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
135.0 all locations
-
Mounting Facility Type And Quantity
4 threaded hole
-
Thread Quantity Per Inch
32
-
Circuit Protection Type
overcurrent all locations