2263SHK15-0-45
Circuit Breakers
CIRCUIT BREAKER
2263SHK15-0-45
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Terminal Type And Quantity
4 threaded stud
-
Thread Series Designator
unc
-
Frequency In Hertz
60.0
-
Switch Voltage Rating And Type In Volts
250.0 ac and 125.0 dc
-
Switch Terminal Type
tab,solder lug
-
Inclosure Protection Type For Which Designed
dustproof and fungus proof
-
Auxiliary Switch Function And Quantity
1 alarm
-
Actuator Position Designation
between pole one and two
-
Manual Actuator Type And Quantity
1 toggle
-
Main Contact Tripping Mechanism Type
trip free
-
Reset Method
manual
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0
-
Trip Release Characteristic
time delay
-
Trip Release Method
magnetic-hydraulic
-
Operating Voltage Type And Rating Per Pole In Volts
250.0 ac
-
Maximum Continuous Load Current Rating Per Pole
15.0 amperes ac
-
Thread Quantity Per Inch
32
-
Storage Type
general purpose warehouse
-
Mounting Facility Type And Quantity
4 threaded hole and 2 unthreaded hole
-
Arc Quenching Method
magnetic blowout
-
Fragility Factor
moderately rugged
-
Switch Contact Arrangement
single pole,double throw
-
Case Material
plastic
-
Center To Center Distance Between Terminals Parallel To Width
0.974 inches minimum and 0.994 inches maximum
-
Center To Center Distance Between Terminals Parallel To Length
4.349 inches minimum and 4.369 inches maximum
-
Body Height
2.677 inches minimum and 2.697 inches maximum
-
Body Width
1.990 inches minimum and 2.010 inches maximum
-
Body Length
5.240 inches minimum and 5.260 inches maximum
-
Switch Current Rating And Type In Amps
15.0 ac and 15.0 dc
-
Trip Delay Time In Seconds Per Rated Continuous Current
40.000 minimum at 200 pct and 120.000 maximum at 200 pct
-
Switch Location And Position Designation
internal at pole one
-
Nominal Thread Size
0.164 inches
-
Internal Trip Release Configuration
series trip
-
Actuator Function
trip-reset
-
Circuit Protection Type
overcurrent
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
5000.0 ac
-
Pole Quantity
2
-
Boss Height
0.208 inches minimum and 0.228 inches maximum
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Width
0.990 inches minimum and 1.010 inches maximum
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
3.052 inches minimum and 3.072 inches maximum
-
Unthreaded Mounting Hole Diameter
0.190 inches nominal