AM44MG6-10-250VAC60C5

Circuit Breakers

CIRCUIT BREAKER

AM44MG6-10-250VAC60C5

5925-00-065-8861

5925 - Circuit Breakers

Eaton Corp

CIRCUIT BREAKER

ACT NOW! SUBMIT A QUICK QUOTE.

Technical Characteristics

  • Mounting Surface To Terminal End Distance

    2.461 inches minimum and 2.481 inches maximum

  • Mounting Facility Type And Quantity

    4 threaded hole

  • Thread Quantity Per Inch

    32

  • Center To Center Distance Between Terminals Parallel To Length

    1.928 inches minimum and 1.948 inches maximum

  • Storage Type

    general purpose warehouse

  • Trip Release Characteristic

    time delay all locations

  • Actuator Function

    trip-reset

  • Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps

    1000.0 ac all locations

  • Trip Release Method

    magnetic-hydraulic all locations

  • Body Style

    multipole-multiple actuator type

  • Unpackaged Unit Weight

    6.500 ounces

  • Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent

    125.0 all locations

  • Inclosure Protection Type For Which Designed

    fungus resistant and moisture resistant

  • Maximum Continuous Load Current Rating Per Pole

    10.0 amperes ac all locations

  • Nominal Thread Size

    0.138 inches

  • Center To Center Distance Between Terminals Parallel To Width

    0.740 inches minimum and 0.760 inches maximum

  • Body Width

    1.490 inches minimum and 1.510 inches maximum

  • Frequency In Hertz

    60.0 all locations

  • Main Contact Tripping Mechanism Type

    trip free

  • Arc Quenching Method

    magnetic blowout

  • Internal Trip Release Configuration

    series trip w/auxiliary load terminal all locations

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Length

    2.052 inches minimum and 2.072 inches maximum

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Width

    0.740 inches minimum and 0.760 inches maximum

  • Operating Voltage Type And Rating Per Pole In Volts

    250.0 ac all locations

  • Manual Actuator Type And Quantity

    2 toggle

  • Body Length

    2.490 inches minimum and 2.510 inches maximum

  • External Actuator Linkage Arrangement

    one and two linked

  • Trip Delay Time In Seconds Per Rated Continuous Current

    0.320 minimum at 200 pct all locations and 1.000 maximum at 200 pct all locations

  • Boss Height

    0.130 inches minimum and 0.150 inches maximum

  • Case Material

    plastic

  • Terminal Type And Quantity

    6 threaded stud

  • Fragility Factor

    moderately rugged

  • Circuit Protection Type

    overcurrent all locations

  • Pole Quantity

    2

  • Thread Series Designator

    unc

  • Actuator Position Designation

    at each pole

  • Reset Method

    manual

Certified to
AS6081 Methods

Implementing Quality Procurement

A rigorous vendor selection process and vendor management system are essential to ensuring quality.
Read more...

Supplying Quality Products

We take every measure to ensure that we supply quality, authentic parts including a strict vendor selection process and rigorous product inspections..
Read more...

Providing Quality People

Our team of dedicated account managers, procurement professionals and specialized inspectors is the most valuable resource we have.
Read more...