3XAM1516-70-250VAC60C1
Circuit Breakers
CIRCUIT BREAKER
3XAM1516-70-250VAC60C1
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Mounting Surface To Terminal End Distance
3.239 inches nominal
-
Pole Quantity
3
-
Mounting Facility Type And Quantity
6 threaded hole
-
Thread Quantity Per Inch
32
-
Maximum Continuous Load Current Rating Per Pole
70.0 amperes ac all locations
-
Operating Voltage Type And Rating Per Pole In Volts
250.0 ac all locations
-
Center To Center Distance Between Terminals Parallel To Width
1.021 inches minimum and
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
2.740 inches minimum and
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
2.760 inches maximum
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Width
1.041 inches maximum
-
Boss Height
0.146 inches minimum and
-
Boss Height
0.166 inches maximum
-
Body Style
8c multipole-multiple actuator type
-
Body Length
3.729 inches maximum
-
Body Width
3.062 inches maximum
-
Case Material
plastic
-
Center To Center Distance Between Terminals Parallel To Length
3.053 inches minimum and
-
Center To Center Distance Between Terminals Parallel To Length
3.073 inches maximum
-
Center To Center Distance Between Terminals Parallel To Width
1.041 inches maximum
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Width
1.021 inches minimum and
-
Iii Fragility Factor
moderately rugged
-
Iii Arc Quenching Method
magnetic blowout
-
Iii Storage Type
general purpose warehouse
-
Trip Release Method
magnetic-hydraulic all locations
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0 all locations
-
Main Contact Tripping Mechanism Type
trip free
-
Manual Actuator Type And Quantity
3 toggle
-
Internal Trip Release Configuration
series trip all locations
-
Trip Delay Time In Seconds Per Rated Continuous Current
105.000 maximum at 200 pct all locations
-
Inclosure Protection Type For Which Designed
fungus proof
-
Thread Series Designator
unc
-
Terminal Type And Quantity
6 threaded stud
-
Body Length
3.709 inches minimum and
-
Body Width
3.042 inches minimum and
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
1500.0 ac all locations
-
Circuit Protection Type
overcurrent all locations
-
Trip Release Characteristic
time delay all locations
-
Reset Method
manual
-
Actuator Function
trip-reset
-
Actuator Position Designation
at each pole
-
External Actuator Linkage Arrangement
one, two, and three linked
-
Nominal Thread Size
0.138 inches
-
Trip Delay Time In Seconds Per Rated Continuous Current
35.000 minimum at 200 pct and
-
Inclosure Protection Type For Which Designed
dustproof and
-
Frequency In Hertz
60.0 all locations