751770

Circuit Breakers

CIRCUIT BREAKER

751770

5925-00-081-4882

5925 - Circuit Breakers

L-3 Communications Cincinnati

CIRCUIT BREAKER

ACT NOW! SUBMIT A QUICK QUOTE.

Technical Characteristics

  • Body Width

    4.125 inches nominal

  • Center To Center Distance Between Terminals Parallel To Width

    1.375 inches nominal

  • Unthreaded Mounting Hole Diameter

    0.196 inches nominal

  • Boss Height

    0.250 inches nominal

  • Pole Quantity

    3

  • Mounting Facility Type And Quantity

    4 unthreaded hole

  • Storage Type

    general purpose warehouse

  • Trip Release Characteristic

    instantaneouss and time delay

  • Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent

    125.0

  • Main Contact Tripping Mechanism Type

    trip free

  • Manual Actuator Type And Quantity

    1 toggle

  • Switch Location And Position Designation

    internal at pole two

  • Trip Delay Time In Seconds Per Rated Continuous Current

    70.000 minimum at 200 pct and 2000.000 maximum at 200 pct

  • Inclosure Protection Type For Which Designed

    fungus resistant and moisture resistant

  • Trip Release Ambient Temp Rating

    40.0 deg celsius nominal

  • Switch Terminal Type

    tab,solder lug

  • Frequency In Hertz

    60.0

  • Terminal Type And Quantity

    6 compression

  • Body Length

    6.062 inches nominal

  • Body Height

    4.375 inches nominal

  • Case Material

    plastic

  • Center To Center Distance Between Terminals Parallel To Length

    5.125 inches nominal

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Length

    5.125 inches nominal

  • Switch Contact Arrangement

    single pole,double throw

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Width

    1.375 inches nominal

  • Thread Quantity Per Inch

    20

  • Maximum Continuous Load Current Rating Per Pole

    225.0 amperes ac

  • Operating Voltage Type And Rating Per Pole In Volts

    600.0 ac

  • Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps

    15000.0 ac

  • Circuit Protection Type

    overcurrent

  • Trip Release Method

    thermal-magnetic

  • Reset Method

    manual

  • Actuator Function

    trip-reset

  • Actuator Position Designation

    at pole two

  • Auxiliary Switch Function And Quantity

    2 control

  • Switch Current Rating And Type In Amps

    6.00 ac and 1.0 dc

  • Switch Voltage Rating And Type In Volts

    250.0 ac and 125.0 dc

Certified to
AS6081 Methods

Implementing Quality Procurement

A rigorous vendor selection process and vendor management system are essential to ensuring quality.
Read more...

Supplying Quality Products

We take every measure to ensure that we supply quality, authentic parts including a strict vendor selection process and rigorous product inspections..
Read more...

Providing Quality People

Our team of dedicated account managers, procurement professionals and specialized inspectors is the most valuable resource we have.
Read more...