HB3Z1-59
Circuit Breakers
CIRCUIT BREAKER
HB3Z1-59
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Test Data Document
81349-mil-c-39019 specification (includes engineering type bulletins, brochures,etc., that reflect specification type data in specification format; excludes commercial catalogs, industry directories, and similar trade publications, reflecting general type
-
Pole Quantity
3
-
Circuit Protection Type
overcurrent all locations
-
Center To Center Distance Between Terminals Parallel To Width
1.250 inches nominal
-
Reset Method
manual
-
Trip Release Characteristic
time delay all locations
-
Actuator Function
trip-reset
-
Trip Delay Time In Seconds Per Rated Continuous Current
0.055 minimum at 200 pct all locations and 0.950 maximum at 200 pct all locations and 0.240 maximum at 400 pct all locations
-
Mounting Surface To Terminal End Distance
1.828 inches maximum
-
Internal Trip Release Configuration
series trip all locations
-
Inclosure Protection Type For Which Designed
fungus resistant and hermetically sealed
-
Nominal Thread Size
0.375 inches
-
Thread Quantity Per Inch
32
-
Operating Voltage Type And Rating Per Pole In Volts
240.0 ac all locations
-
Trip Release Method
magnetic all locations
-
Mounting Facility Type And Quantity
1 threaded bushing
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0 all locations
-
Actuator Position Designation
at pole two
-
Body Style
multipole-single actuator type
-
Case Material
metal
-
Maximum Continuous Load Current Rating Per Pole
10.0 amperes ac all locations
-
Manual Actuator Type And Quantity
1 toggle
-
Body Width
1.937 inches maximum
-
Main Contact Tripping Mechanism Type
trip free
-
Body Length
1.562 inches maximum
-
Center To Center Distance Between Terminals Parallel To Length
0.906 inches maximum
-
Ultimate Trip Time Per Pole In Seconds
0.200 minimum all locations and 7.000 maximum all locations
-
Frequency In Hertz
400.0 all locations
-
Thread Series Designator
unef
-
Terminal Type And Quantity
6 wire hook
-
Bushing Length
0.380 inches maximum
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
300.0 ac all locations
-
~1
data on certain environmental and performanc