HF631020-50DEGC

Circuit Breakers

CIRCUIT BREAKER

HF631020-50DEGC

5925-00-085-0676

5925 - Circuit Breakers

Challenger Electrical Equipment Corp

CIRCUIT BREAKER

ACT NOW! SUBMIT A QUICK QUOTE.

Technical Characteristics

  • Body Style

    13b multipole-single actuator type

  • Body Length

    9.500 inches nominal

  • Body Height

    4.062 inches nominal

  • Case Material

    plastic

  • Center To Center Distance Between Terminals Parallel To Length

    8.000 inches nominal

  • Iii Fragility Factor

    moderately rugged

  • Mounting Facility Type And Quantity

    4 unthreaded hole

  • Iii Storage Type

    general purpose warehouse

  • Operating Voltage Type And Rating Per Pole In Volts

    600.0 ac all locations

  • Circuit Protection Type

    overcurrent all locations

  • Trip Release Method

    thermal-magnetic all locations

  • Reset Method

    manual

  • Main Contact Tripping Mechanism Type

    trip free

  • Terminal Type And Quantity

    6 compression

  • Body Width

    4.125 inches nominal

  • Center To Center Distance Between Terminals Parallel To Width

    1.375 inches nominal

  • Unthreaded Mounting Hole Diameter

    0.219 inches nominal

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Length

    7.250 inches nominal

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Width

    1.375 inches nominal

  • Boss Height

    0.250 inches nominal

  • Pole Quantity

    3

  • Maximum Continuous Load Current Rating Per Pole

    20.0 amperes ac all locations

  • Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps

    20000.0 ac all locations

  • Trip Release Characteristic

    instantaneous all locations

  • Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent

    125.0 all locations

  • Manual Actuator Type And Quantity

    1 toggle

  • Actuator Function

    trip-reset

  • Actuator Position Designation

    at pole two

  • Inclosure Protection Type For Which Designed

    fungus resistant

  • Trip Release Ambient Temp Rating

    50.0 deg celsius maximum all locations

  • Frequency In Hertz

    60.0 all locations

Certified to
AS6081 Methods

Implementing Quality Procurement

A rigorous vendor selection process and vendor management system are essential to ensuring quality.
Read more...

Supplying Quality Products

We take every measure to ensure that we supply quality, authentic parts including a strict vendor selection process and rigorous product inspections..
Read more...

Providing Quality People

Our team of dedicated account managers, procurement professionals and specialized inspectors is the most valuable resource we have.
Read more...