FA3050V
Circuit Breakers
CIRCUIT BREAKER
FA3050V
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Body Width
4.125 inches nominal
-
Case Material
plastic
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Width
1.375 inches nominal
-
Pole Quantity
3
-
Mounting Facility Type And Quantity
4 unthreaded hole
-
Storage Type
general purpose warehouse
-
Trip Release Method
thermal-magnetic
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0
-
Manual Actuator Type And Quantity
1 toggle
-
Actuator Function
trip-reset
-
Actuator Position Designation
at pole two
-
Inclosure Protection Type For Which Designed
fungus resistant
-
Body Length
6.500 inches nominal
-
Body Height
3.375 inches nominal
-
Center To Center Distance Between Terminals Parallel To Length
5.569 inches nominal
-
Center To Center Distance Between Terminals Parallel To Width
1.375 inches nominal
-
Unthreaded Mounting Hole Diameter
0.187 inches nominal
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
4.937 inches nominal
-
Fragility Factor
moderately rugged
-
Boss Height
0.125 inches nominal
-
Maximum Continuous Load Current Rating Per Pole
50.0 amperes ac
-
Operating Voltage Type And Rating Per Pole In Volts
600.0 ac
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
15000.0 ac
-
Circuit Protection Type
overcurrent
-
Trip Release Characteristic
time delay
-
Reset Method
manual
-
Main Contact Tripping Mechanism Type
trip free
-
Trip Delay Time In Seconds Per Rated Continuous Current
45.000 minimum at 200 pct and 150.000 maximum at 200 pct
-
Trip Release Ambient Temp Rating
50.0 deg celsius maximum
-
Frequency In Hertz
60.0
-
Terminal Type And Quantity
6 compression