ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Actuator Position Designation
at each pole
-
Auxiliary Switch Function And Quantity
1 control
-
Nominal Thread Size
0.138 inches
-
Switch Location And Position Designation
internal at pole one
-
Trip Delay Time In Seconds Per Rated Continuous Current
0.500 minimum at 200 pct and 0.900 maximum at 200 pct
-
Switch Terminal Type
tab,solder lug
-
Switch Current Rating And Type In Amps
5.0 ac
-
Frequency In Hertz
400.0
-
Terminal Type And Quantity
4 threaded stud
-
Body Length
2.530 inches nominal
-
Body Width
1.530 inches nominal
-
Case Material
plastic
-
Switch Contact Arrangement
single pole,double throw
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Width
0.750 inches nominal
-
Mounting Surface To Terminal End Distance
2.630 inches nominal
-
Pole Quantity
2
-
Mounting Facility Type And Quantity
4 threaded hole
-
Storage Type
general purpose warehouse
-
Trip Release Method
magnetic
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
150.0
-
Ultimate Trip Time Per Pole In Seconds
1.000 minimum and 8.000 maximum
-
Main Contact Tripping Mechanism Type
trip free
-
Manual Actuator Type And Quantity
2 toggle
-
External Actuator Linkage Arrangement
one and two linked
-
Internal Trip Release Configuration
series trip
-
Inclosure Protection Type For Which Designed
fungus resistant and moisture resistant
-
Switch Voltage Rating And Type In Volts
125.0 ac
-
Thread Series Designator
unc
-
Center To Center Distance Between Terminals Parallel To Length
1.940 inches nominal
-
Center To Center Distance Between Terminals Parallel To Width
any acceptable
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
2.060 inches nominal
-
Boss Height
0.150 inches nominal
-
Thread Quantity Per Inch
32
-
Maximum Continuous Load Current Rating Per Pole
3.5 amperes ac
-
Operating Voltage Type And Rating Per Pole In Volts
250.0 ac
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
1000.0 ac
-
Circuit Protection Type
overcurrent
-
Trip Release Characteristic
time delay
-
Reset Method
manual
-
Actuator Function
trip-reset