711503-1
Circuit Breakers
CIRCUIT BREAKER
711503-1
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Fragility Factor
moderately rugged
-
Special Handling Feature
magnetic
-
Pole Quantity
3
-
Boss Height
0.180 inches minimum and 0.200 inches maximum
-
Circuit Protection Type
overcurrent all locations
-
Maximum Continuous Load Current Rating Per Pole
50.0 amperes ac all locations
-
Thread Series Designator
unc
-
Reset Method
manual
-
Center To Center Distance Between Terminals Parallel To Width
1.370 inches minimum and 1.390 inches maximum
-
Storage Type
general purpose warehouse
-
Trip Release Characteristic
time delay all locations
-
Actuator Function
trip-reset
-
Operating Voltage Type And Rating Per Pole In Volts
240.0 ac all locations
-
Trip Release Method
thermal-magnetic all locations
-
Mounting Facility Type And Quantity
5 unthreaded hole and 6 threaded hole
-
Actuator Position Designation
at pole two
-
Trip Release Ambient Temp Rating
50.0 deg celsius nominal all locations
-
Body Style
multipole-single actuator type
-
Body Height
3.180 inches minimum and 3.200 inches maximum
-
Manual Actuator Type And Quantity
1 toggle
-
Thread Quantity Per Inch
20
-
Terminal Type And Quantity
6 compression
-
Main Contact Tripping Mechanism Type
trip free
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
4.710 inches minimum and 4.730 inches maximum
-
Center To Center Distance Between Terminals Parallel To Length
5.240 inches minimum and 5.260 inches maximum
-
Unthreaded Mounting Hole Diameter
0.188 inches nominal
-
Body Width
4.115 inches minimum and 4.135 inches maximum
-
Inclosure Protection Type For Which Designed
shock resistant and vibration resistant and moisture resistant and sand resistant and fungus resistant and salt spray proof and dustproof
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
7500.0 ac all locations
-
Frequency In Hertz
400.0 all locations
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
140.0 all locations
-
Nominal Thread Size
0.250 inches
-
Body Length
5.990 inches minimum and 6.010 inches maximum
-
Trip Delay Time In Seconds Per Rated Continuous Current
30.000 minimum at 200 pct all locations and 100.000 maximum at 200 pct all locations
-
Case Material
plastic
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Width
1.370 inches minimum and 1.390 inches maximum