Technical Characteristics

  • Body Width

    1.520 inches nominal

  • Mounting Surface To Terminal End Distance

    2.000 inches nominal

  • Maximum Continuous Load Current Rating Per Pole

    5.0 amperes ac all locations

  • Nominal Thread Size

    0.138 inches

  • Frequency In Hertz

    60.0 all locations

  • Center To Center Distance Between Terminals Parallel To Length

    1.190 inches nominal

  • Main Contact Tripping Mechanism Type

    trip free

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Width

    0.750 inches nominal

  • Arc Quenching Method

    magnetic blowout

  • Body Length

    2.500 inches nominal

  • Center To Center Distance Between Terminals Parallel To Width

    0.750 inches nominal

  • Circuit Protection Type

    overcurrent all locations

  • Pole Quantity

    2

  • Thread Series Designator

    unc

  • Actuator Position Designation

    at each pole

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Length

    1.812 inches nominal

  • Reset Method

    manual

  • Storage Type

    general purpose warehouse

  • Trip Release Characteristic

    time delay all locations

  • Actuator Function

    trip-reset

  • Inclosure Protection Type For Which Designed

    explosion resistant

  • Internal Trip Release Configuration

    series trip all locations

  • Terminal Type And Quantity

    4 screw

  • Mounting Facility Type And Quantity

    4 threaded hole

  • Thread Quantity Per Inch

    32

  • Trip Release Method

    magnetic-hydraulic all locations

  • Body Style

    multipole-multiple actuator type

  • Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent

    125.0 all locations

  • Trip Delay Time In Seconds Per Rated Continuous Current

    3.500 minimum at 200 pct all locations and 12.000 maximum at 200 pct all locations

  • Manual Actuator Type And Quantity

    2 toggle

  • Operating Voltage Type And Rating Per Pole In Volts

    120.0 ac all locations

  • Unpackaged Unit Weight

    8.750 ounces

  • Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps

    3500.0 ac all locations

  • External Actuator Linkage Arrangement

    one and two linked

  • Case Material

    plastic

Certified to
AS6081 Methods

Implementing Quality Procurement

A rigorous vendor selection process and vendor management system are essential to ensuring quality.
Read more...

Supplying Quality Products

We take every measure to ensure that we supply quality, authentic parts including a strict vendor selection process and rigorous product inspections..
Read more...

Providing Quality People

Our team of dedicated account managers, procurement professionals and specialized inspectors is the most valuable resource we have.
Read more...