SMA724799
Circuit Breakers
CIRCUIT BREAKER
SMA724799
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Center To Center Distance Between Terminals Parallel To Length
4.750 inches nominal
-
Trip Release Method
magnetic all locations
-
Body Style
multipole-multiple actuator type
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0 all locations
-
Switch Contact Arrangement
single pole, double throw
-
Switch Current Rating And Type In Amps
2.5 ac and 1.0 dc
-
Switch Voltage Rating And Type In Volts
250.0 ac and 50.0 dc
-
Trip Delay Time In Seconds Per Rated Continuous Current
5.000 minimum at 200 pct all locations and 20.000 maximum at 200 pct all locations
-
Body Height
2.827 inches nominal
-
Frequency In Hertz
60.0 all locations
-
Terminal Type And Quantity
6 compression
-
Unthreaded Mounting Hole Diameter
0.164 inches nominal
-
Main Contact Tripping Mechanism Type
trip free
-
Arc Quenching Method
magnetic blowout
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
5000.0 ac all locations
-
Switch Terminal Type
pin
-
Auxiliary Switch Function And Quantity
1 alarm
-
Unpackaged Unit Weight
2.250 pounds
-
Manual Actuator Type And Quantity
3 toggle
-
Mounting Facility Type And Quantity
3 slot and 3 unthreaded hole
-
Body Width
3.103 inches maximum
-
Switch Location And Position Designation
internal at pole one
-
Case Material
plastic
-
Body Length
5.844 inches nominal
-
Fragility Factor
moderately rugged
-
Mounting Slot Width
0.200 inches nominal
-
Special Handling Feature
magnetic
-
Pole Quantity
3
-
Circuit Protection Type
overcurrent all locations
-
Actuator Position Designation
at each pole
-
Reset Method
manual
-
Center To Center Distance Between Terminals Parallel To Width
1.026 inches nominal
-
Inclosure Protection Type For Which Designed
general purpose and hermetically sealed
-
Storage Type
general purpose warehouse
-
Maximum Continuous Load Current Rating Per Pole
100.0 amperes ac all locations
-
Trip Release Characteristic
time delay all locations
-
Actuator Function
trip-reset
-
External Actuator Linkage Arrangement
one, two, and three linked
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
5.032 inches nominal
-
Internal Trip Release Configuration
series trip all locations
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Width
1.026 inches nominal
-
Operating Voltage Type And Rating Per Pole In Volts
240.0 ac all locations