TEB-124030WL

Circuit Breakers

CIRCUIT BREAKER

TEB-124030WL

5925-00-139-2676

5925 - Circuit Breakers

General Electric Co

CIRCUIT BREAKER

ACT NOW! SUBMIT A QUICK QUOTE.

Technical Characteristics

  • Fragility Factor

    moderately rugged

  • Circuit Protection Type

    overcurrent all locations

  • Pole Quantity

    2

  • Reset Method

    manual

  • Actuator Position Designation

    at pole one

  • Maximum Continuous Load Current Rating Per Pole

    30.0 amperes ac single location and 30.0 amperes dc single location

  • Storage Type

    general purpose warehouse

  • Actuator Function

    trip-reset

  • Body Length

    6.312 inches nominal

  • Trip Release Characteristic

    instantaneous all locations and time delay all locations

  • Center To Center Distance Between Terminals Parallel To Width

    1.375 inches nominal

  • Body Width

    2.750 inches nominal

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Width

    1.380 inches nominal

  • Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent

    125.0 all locations

  • Trip Release Method

    thermal-magnetic all locations

  • Trip Release Ambient Temp Rating

    50.0 deg celsius nominal all locations

  • Body Style

    multipole-single actuator type

  • Operating Voltage Type And Rating Per Pole In Volts

    480.0 ac single location and 250.0 dc single location

  • Mounting Slot Width

    0.188 inches nominal

  • Terminal Type And Quantity

    4 compression

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Length

    4.880 inches nominal

  • Arc Quenching Method

    deion

  • Mounting Facility Type And Quantity

    4 slot and 2 unthreaded hole

  • Manual Actuator Type And Quantity

    1 toggle

  • Frequency In Hertz

    60.0 all locations

  • Main Contact Tripping Mechanism Type

    trip free

  • Boss Height

    0.125 inches nominal

  • Inclosure Protection Type For Which Designed

    general purpose

  • Cubic Measure

    55.319 cubic inches

  • Unthreaded Mounting Hole Diameter

    0.188 inches nominal

  • Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps

    14000.0 ac all locations and 10000.0 dc all locations

  • Center To Center Distance Between Terminals Parallel To Length

    5.250 inches nominal

  • Trip Delay Time In Seconds Per Rated Continuous Current

    0.540 maximum at 200 pct all locations

  • Case Material

    plastic

  • Body Height

    3.187 inches nominal

Certified to
AS6081 Methods

Implementing Quality Procurement

A rigorous vendor selection process and vendor management system are essential to ensuring quality.
Read more...

Supplying Quality Products

We take every measure to ensure that we supply quality, authentic parts including a strict vendor selection process and rigorous product inspections..
Read more...

Providing Quality People

Our team of dedicated account managers, procurement professionals and specialized inspectors is the most valuable resource we have.
Read more...