0005-644-004

Circuit Breakers

CIRCUIT BREAKER

0005-644-004

5925-00-147-0749

5925 - Circuit Breakers

Spx Corporation

CIRCUIT BREAKER

ACT NOW! SUBMIT A QUICK QUOTE.

Technical Characteristics

  • Fragility Factor

    moderately rugged

  • Special Handling Feature

    magnetic

  • Circuit Protection Type

    overcurrent all locations

  • Center To Center Distance Between Terminals Parallel To Width

    0.735 inches minimum and 0.765 inches maximum

  • Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps

    2000.0 dc all locations

  • Pole Quantity

    2

  • Trip Delay Time In Seconds Per Rated Continuous Current

    0.100 minimum at 200 pct all locations and 1.700 maximum at 200 pct all locations

  • Unpackaged Unit Weight

    7.400 ounces

  • Terminal Type And Quantity

    4 threaded stud

  • External Actuator Linkage Arrangement

    one and two linked

  • Case Material

    plastic

  • Thread Series Designator

    unc

  • Actuator Position Designation

    at each pole

  • Reset Method

    manual

  • Inclosure Protection Type For Which Designed

    shockproof and vibrationproof and moisture resistant and corrosion resistant and fungus resistant

  • Boss Height

    0.150 inches nominal

  • Storage Type

    general purpose warehouse

  • Trip Release Characteristic

    time delay all locations

  • Actuator Function

    trip-reset

  • Maximum Continuous Load Current Rating Per Pole

    100.0 milliamperes dc second location

  • Internal Trip Release Configuration

    series trip all locations

  • Center To Center Distance Between Terminals Parallel To Length

    1.940 inches nominal

  • Mounting Facility Type And Quantity

    4 threaded hole

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Length

    2.050 inches minimum and 2.070 inches maximum

  • Thread Quantity Per Inch

    32

  • Switch Current Rating And Type In Amps

    10.0 ac and 10.0 dc

  • Trip Release Method

    magnetic all locations

  • Body Style

    multipole-multiple actuator type

  • Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent

    125.0 all locations

  • Switch Contact Arrangement

    single pole, double throw

  • Switch Voltage Rating And Type In Volts

    250.0 ac and 65.0 dc

  • Maximum Continuous Load Current Rating Per Pole

    50.0 amperes dc first location

  • Nominal Thread Size

    0.138 inches

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Width

    0.735 inches minimum and 0.765 inches maximum

  • Main Contact Tripping Mechanism Type

    trip free

  • Arc Quenching Method

    magnetic blowout

  • Operating Voltage Type And Rating Per Pole In Volts

    32.0 dc all locations

  • Switch Location And Position Designation

    internal at each pole

  • Manual Actuator Type And Quantity

    2 toggle

  • Body Width

    1.515 inches maximum

  • Switch Terminal Type

    pin

  • Thread Pitch Diameters

    +0.1177/+0.1214 inches

  • Body Length

    2.480 inches minimum and 2.500 inches maximum

  • Mounting Surface To Terminal End Distance

    2.625 inches maximum

  • Auxiliary Switch Function And Quantity

    1 alarm

Certified to
AS6081 Methods

Implementing Quality Procurement

A rigorous vendor selection process and vendor management system are essential to ensuring quality.
Read more...

Supplying Quality Products

We take every measure to ensure that we supply quality, authentic parts including a strict vendor selection process and rigorous product inspections..
Read more...

Providing Quality People

Our team of dedicated account managers, procurement professionals and specialized inspectors is the most valuable resource we have.
Read more...