SM-A-742929-3
Circuit Breakers
CIRCUIT BREAKER
SM-A-742929-3
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Inclosure Protection Type For Which Designed
salt spray proof and moisture resistant and vibration resistant and shock resistant and fungus resistant
-
Trip Delay Time In Seconds Per Rated Continuous Current
30.000 minimum at 200 pct first location and 100.000 maximum at 200 pct first location
-
Auxiliary Switch Function And Quantity
1 alarm
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
2.750 inches nominal
-
Mounting Slot Width
0.164 inches nominal
-
External Actuator Linkage Arrangement
one and two linked
-
Operating Voltage Type And Rating Per Pole In Volts
30.0 dc second location
-
Switch Voltage Rating And Type In Volts
125.0 ac
-
Switch Location And Position Designation
internal at pole one
-
Case Material
plastic
-
Terminal Type And Quantity
6 threaded stud
-
Fragility Factor
moderately rugged
-
Switch Terminal Type
tab, solder lug
-
Special Handling Feature
magnetic
-
Mounting Facility Type And Quantity
4 threaded hole and 4 slot
-
Internal Trip Release Configuration
relay trip second location
-
Pole Quantity
2
-
Thread Series Designator
unc
-
Unpackaged Unit Weight
1.300 pounds
-
Manual Actuator Type And Quantity
2 toggle
-
Operating Voltage Type And Rating Per Pole In Volts
125.0 dc first location
-
Body Length
4.750 inches nominal
-
Switch Current Rating And Type In Amps
5.0 ac
-
Actuator Position Designation
at each pole
-
Reset Method
manual
-
Center To Center Distance Between Terminals Parallel To Width
1.026 inches nominal
-
Circuit Protection Type
overcurrent first location
-
Storage Type
general purpose warehouse
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
5000.0 dc all locations
-
Actuator Function
trip-reset
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Width
1.026 inches nominal
-
Thread Quantity Per Inch
32
-
Trip Release Method
magnetic all locations
-
Body Style
multipole-multiple actuator type
-
Internal Trip Release Configuration
series trip first location
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0 first location
-
Trip Release Characteristic
time delay first location
-
Maximum Continuous Load Current Rating Per Pole
50.0 amperes dc all locations
-
Mounting Surface To Terminal End Distance
3.485 inches nominal
-
Switch Contact Arrangement
single pole, double throw
-
Body Width
2.072 inches maximum
-
Trip Release Characteristic
instantaneous second location
-
Test Data Document
80063-sm-a-742924 drawing (this is the basic governing drawing, such as a contractor drawing, original equipment manufacturer drawing, etc.; excludes any specification, standard or other document that may be referenced in a basic governing drawing)
-
Nominal Thread Size
0.138 inches
-
Center To Center Distance Between Terminals Parallel To Length
3.547 inches nominal
-
Main Contact Tripping Mechanism Type
trip free
-
Circuit Protection Type
overvoltage second location
-
Boss Height
0.219 inches nominal