B248-13781G2
Circuit Breakers
CIRCUIT BREAKER
B248-13781G2
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Overall Length
2.188 inches nominal
-
Thread Series Designator
unc
-
Reset Method
manual
-
Actuator Function
trip-reset
-
Terminal Type And Quantity
2 screw
-
Overall Width
0.750 inches nominal
-
Thread Quantity Per Inch
32
-
Circuit Protection Type
overcurrent single location
-
Trip Release Method
thermal single location
-
Maximum Continuous Load Current Rating Per Pole
20.0 amperes dc single location
-
Manual Actuator Type And Quantity
1 push-pull
-
Main Contact Tripping Mechanism Type
nontrip free
-
Pole Quantity
1
-
Nominal Thread Size
0.138 inches
-
Trip Delay Time In Seconds Per Rated Continuous Current
10.000 minimum at 200 pct single location and 100.000 maximum at 200 pct single location
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
1500.0 dc single location
-
Trip Release Characteristic
time delay single location
-
Trip Release Ambient Temp Rating
25.0 deg celsius nominal single location
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
138.0 single location
-
Nondefinitive Spec/Std Data
3161-+20 type
-
Overall Height
2.625 inches nominal
-
Operating Voltage Type And Rating Per Pole In Volts
30.0 dc single location
-
Case Material
plastic