93905
Circuit Breakers
CIRCUIT BREAKER
93905
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Body Style
multipole-single actuator type
-
Body Length
10.250 inches nominal
-
Case Material
metal
-
Center To Center Distance Between Terminals Parallel To Length
8.750 inches nominal
-
Unthreaded Mounting Hole Diameter
0.438 inches nominal
-
Boss Height
0.312 inches nominal
-
Mounting Surface To Terminal End Distance
8.625 inches nominal
-
Mounting Facility Type And Quantity
4 unthreaded hole
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
4000.0 ac
-
Trip Release Method
magnetic
-
Trip Release Characteristic
time delay
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
300.0
-
Actuator Function
trip-reset
-
Actuator Position Designation
at each pole
-
Internal Trip Release Configuration
series trip
-
Body Width
5.000 inches nominal
-
Center To Center Distance Between Terminals Parallel To Width
1.625 inches nominal
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
8.750 inches nominal
-
Trip Delay Time In Seconds Per Rated Continuous Current
0.100 nominal at 150 pct and 0.900 nominal at 200 pct and 0.034 nominal at 300 pct
-
Terminal Type And Quantity
6 threaded stud
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Width
3.250 inches nominal
-
Pole Quantity
3
-
Maximum Continuous Load Current Rating Per Pole
100.0 amperes ac
-
Operating Voltage Type And Rating Per Pole In Volts
500.0 ac
-
Circuit Protection Type
overcurrent
-
Reset Method
manual
-
Main Contact Tripping Mechanism Type
trip free
-
Manual Actuator Type And Quantity
1 toggle
-
Frequency In Hertz
60.0