Technical Characteristics

  • Trip Release Characteristic

    time delay single location

  • Fragility Factor

    moderately rugged

  • Switch Terminal Type

    tab, solder lug

  • Thread Series Designator

    unc

  • Reset Method

    manual

  • Actuator Position Designation

    at pole one

  • Storage Type

    general purpose warehouse

  • Body Width

    0.750 inches nominal

  • Actuator Function

    trip-reset

  • Mounting Facility Type And Quantity

    2 threaded hole

  • Thread Quantity Per Inch

    32

  • Circuit Protection Type

    overcurrent single location

  • Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent

    125.0 single location

  • Main Contact Tripping Mechanism Type

    trip free

  • Body Length

    2.500 inches nominal

  • Boss Height

    0.140 inches nominal

  • Trip Delay Time In Seconds Per Rated Continuous Current

    0.250 minimum at 200 pct single location and 0.750 maximum at 200 pct single location

  • Operating Voltage Type And Rating Per Pole In Volts

    50.0 dc single location

  • Body Style

    single pole type

  • Trip Release Method

    magnetic-hydraulic single location

  • Maximum Continuous Load Current Rating Per Pole

    9.0 amperes dc single location

  • Auxiliary Switch Function And Quantity

    1 alarm

  • Inclosure Protection Type For Which Designed

    moisture resistant and fungus resistant

  • Switch Location And Position Designation

    internal at pole one

  • Case Material

    plastic

  • Center To Center Distance Between Terminals Parallel To Length

    1.938 inches nominal

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Length

    2.062 inches nominal

  • Terminal Type And Quantity

    2 threaded stud

  • Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps

    2000.0 dc single location

  • Arc Quenching Method

    air

  • Mounting Surface To Terminal End Distance

    2.611 inches nominal

  • Switch Contact Arrangement

    single pole, double throw

  • Switch Current Rating And Type In Amps

    2.5 ac and 1.0 dc

  • Switch Voltage Rating And Type In Volts

    250.0 ac and 50.0 dc

  • Pole Quantity

    1

  • Manual Actuator Type And Quantity

    1 toggle

  • Internal Trip Release Configuration

    series trip single location

  • Nominal Thread Size

    0.138 inches

Certified to
AS6081 Methods

Implementing Quality Procurement

A rigorous vendor selection process and vendor management system are essential to ensuring quality.
Read more...

Supplying Quality Products

We take every measure to ensure that we supply quality, authentic parts including a strict vendor selection process and rigorous product inspections..
Read more...

Providing Quality People

Our team of dedicated account managers, procurement professionals and specialized inspectors is the most valuable resource we have.
Read more...