AP1-1R4-2-251
Circuit Breakers
CIRCUIT BREAKER
AP1-1R4-2-251
Sensata Technologies Maryland Inc
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Fragility Factor
moderately rugged
-
Terminal Type And Quantity
2 wire hook
-
Special Handling Feature
magnetic
-
Reset Method
manual
-
Mounting Facility Type And Quantity
1 threaded bushing w/panel seal
-
Actuator Position Designation
at pole one
-
Unpackaged Unit Weight
2.100 ounces
-
Storage Type
general purpose warehouse
-
Actuator Function
trip-reset
-
Inclosure Protection Type For Which Designed
explosion resistant
-
Switch Voltage Rating And Type In Volts
125.0 ac and 50.0 dc
-
Thread Pitch Diameters
+0.3503/+0.3537 inches
-
Trip Delay Time In Seconds Per Rated Continuous Current
1.000 minimum at 200 pct single location and 4.000 maximum at 200 pct single location
-
Nominal Thread Size
0.375 inches
-
Maximum Continuous Load Current Rating Per Pole
250.0 milliamperes ac single location
-
Thread Quantity Per Inch
32
-
Circuit Protection Type
overcurrent single location
-
Internal Trip Release Configuration
series trip single location
-
Switch Location And Position Designation
external at pole one
-
Body Length
1.500 inches maximum
-
Trip Release Characteristic
time delay single location
-
Main Contact Tripping Mechanism Type
trip free
-
Arc Quenching Method
magnetic blowout
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
300.0 ac single location
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
115.0 single location
-
Switch Terminal Type
double screw
-
Frequency In Hertz
400.0 single location
-
Body Style
single pole type
-
Body Width
0.625 inches maximum
-
Trip Release Method
magnetic-hydraulic single location
-
Mounting Surface To Terminal End Distance
1.605 inches maximum
-
Thread Series Designator
unef
-
Switch Current Rating And Type In Amps
1.0 ac and 0.5 dc
-
Auxiliary Switch Function And Quantity
1 control
-
Manual Actuator Type And Quantity
1 toggle
-
Case Material
metal
-
Pole Quantity
1
-
Bushing Length
0.375 inches maximum
-
Center To Center Distance Between Terminals Parallel To Length
0.875 inches nominal
-
Switch Contact Arrangement
single pole, double throw
-
Operating Voltage Type And Rating Per Pole In Volts
250.0 ac single location
-
Ultimate Trip Time Per Pole In Seconds
6.500 minimum single location and 30.000 maximum single location