E3100A
Circuit Breakers
CIRCUIT BREAKER
E3100A
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Operating Voltage Type And Rating Per Pole In Volts
240.0 ac all locations and 250.0 dc all locations
-
Case Material
plastic
-
Trip Release Method
thermal-magnetic all locations
-
Manual Actuator Type And Quantity
1 toggle
-
Frequency In Hertz
60.0 all locations
-
Main Contact Tripping Mechanism Type
trip free
-
Terminal Type And Quantity
6 screw
-
Unthreaded Mounting Hole Diameter
0.188 inches nominal
-
Trip Delay Time In Seconds Per Rated Continuous Current
110.000 nominal at 200 pct all locations and 7200.000 nominal at 125 pct all locations and 23.000 nominal at 300 pct all locations
-
Trip Release Ambient Temp Rating
25.0 deg celsius maximum all locations
-
Mounting Facility Type And Quantity
6 unthreaded hole
-
Pole Quantity
3
-
Circuit Protection Type
overcurrent all locations
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
5000.0 ac all locations and 5000.0 dc all locations
-
Actuator Function
trip w/separate reset
-
Actuator Position Designation
at each pole
-
Reset Method
manual
-
Maximum Continuous Load Current Rating Per Pole
100.0 amperes ac all locations and 100.0 amperes dc all locations
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0 all locations
-
Trip Release Characteristic
instantaneous all locations and time delay all locations