Technical Characteristics
-
Body Length
2.530 inches maximum
-
Body Width
1.495 inches minimum and 1.505 inches maximum
-
Center To Center Distance Between Terminals Parallel To Length
1.928 inches minimum and 1.948 inches maximum
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
2.055 inches minimum and 2.065 inches maximum
-
Arc Quenching Method
magnetic blowout
-
Storage Type
general purpose warehouse
-
Thread Quantity Per Inch
32
-
Maximum Continuous Load Current Rating Per Pole
15.0 amperes ac
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
2000.0 ac
-
Case Material
plastic
-
Center To Center Distance Between Terminals Parallel To Width
0.745 inches minimum and 0.755 inches maximum
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Width
0.745 inches minimum and 0.755 inches maximum
-
Fragility Factor
moderately rugged
-
Boss Height
0.125 inches minimum and 0.135 inches maximum
-
Mounting Surface To Terminal End Distance
2.560 inches maximum
-
Pole Quantity
2
-
Mounting Facility Type And Quantity
4 threaded hole
-
Special Handling Feature
magnetic
-
Operating Voltage Type And Rating Per Pole In Volts
125.0 ac
-
Circuit Protection Type
overcurrent
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0
-
Main Contact Tripping Mechanism Type
trip free
-
Internal Trip Release Configuration
series trip
-
Nominal Thread Size
0.138 inches
-
Inclosure Protection Type For Which Designed
vibration resistant and shock resistant and corrosion resistant and moisture resistant
-
Frequency In Hertz
60.0
-
Trip Release Method
magnetic-hydraulic
-
Trip Release Characteristic
time delay
-
Reset Method
manual
-
Manual Actuator Type And Quantity
2 toggle
-
Actuator Function
trip-reset
-
Actuator Position Designation
at each pole
-
External Actuator Linkage Arrangement
one and two linked
-
Trip Delay Time In Seconds Per Rated Continuous Current
0.200 minimum at 200 pct and 1.000 maximum at 200 pct
-
Unpackaged Unit Weight
1.200 pounds
-
Test Data Document
82577-999059 drawing
-
Thread Series Designator
unc
-
Terminal Type And Quantity
4 threaded stud