JA1A3-2-2A
Circuit Breakers
CIRCUIT BREAKER
JA1A3-2-2A
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Body Width
0.750 inches nominal
-
Center To Center Distance Between Terminals Parallel To Length
1.560 inches nominal
-
Mounting Facility Type And Quantity
2 threaded hole
-
Maximum Continuous Load Current Rating Per Pole
2.0 amperes ac single location
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
1000.0 ac single location
-
Trip Release Method
magnetic-hydraulic single location
-
Trip Release Characteristic
time delay single location
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0 single location
-
Actuator Function
trip-reset
-
Internal Trip Release Configuration
series trip single location
-
Nominal Thread Size
0.138 inches
-
Frequency In Hertz
60.0 single location
-
Design Control Reference
653-3-360013-2
-
Terminal Type And Quantity
2 tab, solder lug
-
Body Style
4a single pole type
-
Body Length
2.000 inches nominal
-
Case Material
plastic
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
1.660 inches nominal
-
Mounting Surface To Terminal End Distance
1.880 inches nominal
-
Pole Quantity
1
-
Thread Quantity Per Inch
32
-
Operating Voltage Type And Rating Per Pole In Volts
250.0 ac single location
-
Circuit Protection Type
overcurrent single location
-
Ultimate Trip Time Per Pole In Seconds
3.000 minimum and 50.000 maximum single location
-
Reset Method
manual
-
Main Contact Tripping Mechanism Type
trip free
-
Manual Actuator Type And Quantity
1 toggle
-
Actuator Position Designation
at pole one
-
Trip Delay Time In Seconds Per Rated Continuous Current
2.000 nominal at 200 pct and 0.800 nominal at 300 pct single location
-
Inclosure Protection Type For Which Designed
fungus resistant and moisture resistant
-
Manufacturers Code
50237
-
Thread Series Designator
unc