B4524-7414-1
Circuit Breakers
CIRCUIT BREAKER
B4524-7414-1
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Fragility Factor
moderately rugged
-
Switch Terminal Type
tab, solder lug
-
Pole Quantity
3
-
Circuit Protection Type
overcurrent all locations
-
Switch Voltage Rating And Type In Volts
250.0 ac
-
Thread Series Designator
unc
-
Actuator Position Designation
at each pole
-
Reset Method
manual
-
Mounting Surface To Terminal End Distance
2.461 inches minimum and 2.481 inches maximum
-
Terminal Type And Quantity
6 threaded stud
-
Case Material
plastic
-
Auxiliary Switch Function And Quantity
1 control
-
Body Style
multipole-multiple actuator type
-
Arc Quenching Method
air
-
Trip Release Method
magnetic-hydraulic all locations
-
Body Width
0.740 inches minimum and 0.760 inches maximum
-
Thread Quantity Per Inch
32
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
1000.0 ac all locations
-
Internal Trip Release Configuration
series trip all locations
-
Actuator Function
trip-reset
-
Trip Release Characteristic
time delay all locations
-
Storage Type
general purpose warehouse
-
Center To Center Distance Between Terminals Parallel To Length
1.928 inches minimum and 1.948 inches maximum
-
Boss Height
0.130 inches minimum and 0.150 inches maximum
-
Manual Actuator Type And Quantity
3 toggle
-
Body Length
2.490 inches minimum and 2.510 inches maximum
-
Frequency In Hertz
400.0 all locations
-
Operating Voltage Type And Rating Per Pole In Volts
250.0 ac all locations
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Width
0.740 inches minimum and 0.760 inches maximum
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
2.052 inches minimum and 2.072 inches maximum
-
Main Contact Tripping Mechanism Type
trip free
-
Center To Center Distance Between Terminals Parallel To Width
0.740 inches minimum and 0.760 inches maximum
-
Nominal Thread Size
0.138 inches
-
Trip Delay Time In Seconds Per Rated Continuous Current
2.500 minimum at 200 pct all locations and 8.500 maximum at 200 pct all locations
-
Switch Location And Position Designation
internal between pole one and two
-
Maximum Continuous Load Current Rating Per Pole
54.0 amperes ac all locations
-
Mounting Facility Type And Quantity
6 threaded hole
-
Inclosure Protection Type For Which Designed
fungus resistant and moisture resistant
-
Switch Contact Arrangement
single pole, double throw
-
Switch Current Rating And Type In Amps
2.5 ac
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0 all locations