Technical Characteristics
-
Test Data Document
97403-13216e6205 drawing (this is the basic governing drawing, such as a contractor drawing, original equipment manufacturer drawing, etc.; excludes any specification, standard or other document that may be referenced in a basic governing drawing)
-
Fragility Factor
moderately rugged
-
Center To Center Distance Between Terminals Parallel To Width
0.750 inches nominal
-
Operating Voltage Type And Rating Per Pole In Volts
208.0 ac all locations
-
Special Handling Feature
magnetic
-
Pole Quantity
3
-
Circuit Protection Type
overcurrent all locations
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
1.660 inches nominal
-
Thread Series Designator
unc
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0 all locations
-
Switch Contact Arrangement
single pole, double throw
-
Inclosure Protection Type For Which Designed
fungus resistant and moisture resistant
-
Mounting Facility Type And Quantity
6 threaded hole
-
Actuator Position Designation
at each pole
-
Reset Method
manual
-
Switch Voltage Rating And Type In Volts
125.0 ac and 28.0 dc
-
Terminal Type And Quantity
6 tab, solder lug
-
Storage Type
general purpose warehouse
-
Trip Release Characteristic
time delay all locations
-
Actuator Function
trip-reset
-
Mounting Surface To Terminal End Distance
1.880 inches nominal
-
External Actuator Linkage Arrangement
one, two, and three linked
-
Internal Trip Release Configuration
series trip all locations
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
1000.0 ac all locations
-
Maximum Continuous Load Current Rating Per Pole
20.0 amperes ac all locations
-
Switch Current Rating And Type In Amps
5.0 ac and 5.0 dc
-
Thread Quantity Per Inch
32
-
Body Length
1.985 inches minimum and 2.015 inches maximum
-
Center To Center Distance Between Terminals Parallel To Length
1.789 inches nominal
-
Trip Delay Time In Seconds Per Rated Continuous Current
0.500 minimum at 200 pct all locations and 4.000 maximum at 200 pct all locations
-
Trip Release Method
magnetic-hydraulic all locations
-
Body Style
multipole-multiple actuator type
-
Nominal Thread Size
0.138 inches
-
Body Width
2.250 inches nominal
-
Main Contact Tripping Mechanism Type
trip free
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Width
0.750 inches nominal
-
Arc Quenching Method
magnetic blowout
-
Frequency In Hertz
50.0 all locations or 60.0 all locations
-
Switch Terminal Type
pin
-
Auxiliary Switch Function And Quantity
1 alarm
-
Manual Actuator Type And Quantity
3 toggle
-
Switch Location And Position Designation
internal at pole one
-
Case Material