AM33HEMG6-25-250-16-400
Circuit Breakers
CIRCUIT BREAKER
AM33HEMG6-25-250-16-400
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Body Style
8c multipole-multiple actuator type
-
Body Length
2.530 inches maximum
-
Center To Center Distance Between Terminals Parallel To Width
0.740 inches minimum and 0.760 inches maximum
-
Switch Contact Arrangement
single pole, double throw
-
Iii Fragility Factor
moderately rugged
-
Boss Height
0.067 inches minimum and 0.130 inches maximum
-
Mounting Facility Type And Quantity
4 threaded hole
-
Iii Storage Type
general purpose warehouse
-
Maximum Continuous Load Current Rating Per Pole
25.0 amperes ac and 25.0 amperes dc all locations
-
Operating Voltage Type And Rating Per Pole In Volts
250.0 ac and 50.0 dc all locations
-
Circuit Protection Type
overcurrent all locations
-
Trip Release Method
magnetic all locations
-
Body Width
1.460 inches minimum and 1.500 inches maximum
-
Case Material
plastic
-
Center To Center Distance Between Terminals Parallel To Length
1.930 inches minimum and 1.950 inches maximum
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
2.050 inches minimum and 2.070 inches maximum
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Width
0.740 inches minimum and 0.760 inches maximum
-
Mounting Surface To Terminal End Distance
2.560 inches maximum
-
Pole Quantity
2
-
Iii Special Handling Feature
magnetic
-
Thread Quantity Per Inch
32
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
1000.0 ac and 2000.0 dc all locations
-
Trip Release Characteristic
time delay all locations
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
150.0 all locations
-
Main Contact Tripping Mechanism Type
trip free
-
Manual Actuator Type And Quantity
2 toggle
-
Auxiliary Switch Function And Quantity
1 alarm
-
Internal Trip Release Configuration
series trip all locations
-
Iii Unpackaged Unit Weight
0.750 pounds
-
Thread Series Designator
unc
-
Reset Method
manual
-
Actuator Function
trip-reset
-
Actuator Position Designation
at each pole
-
External Actuator Linkage Arrangement
one and two linked
-
Nominal Thread Size
0.138 inches
-
Switch Location And Position Designation
internal at pole one
-
Trip Delay Time In Seconds Per Rated Continuous Current
0.060 minimum at 200 pct and 0.100 maximum at 200 pct all locations
-
Inclosure Protection Type For Which Designed
vibration resistant and shock resistant and humidity resistant and fungus resistant and salt spray proof
-
Switch Terminal Type
tab w/screw
-
Switch Current Rating And Type In Amps
2.5 ac and 1.0 dc
-
Switch Voltage Rating And Type In Volts
250.0 ac and 50.0 dc
-
Frequency In Hertz
400.0 all locations
-
Terminal Type And Quantity
4 threaded stud