TFK236125WL-TF225D-TN1225
Circuit Breakers
CIRCUIT BREAKER
TFK236125WL-TF225D-TN1225
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Pole Quantity
3
-
Circuit Protection Type
overcurrent all locations
-
Reset Method
manual
-
Trip Release Characteristic
instantaneous all locations and time delay all locations
-
Maximum Continuous Load Current Rating Per Pole
125.0 amperes ac all locations
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0 all locations
-
Trip Release Method
thermal-magnetic all locations
-
Trip Delay Time In Seconds Per Rated Continuous Current
90.000 minimum at 200 pct all locations and 480.000 maximum at 200 pct all locations
-
Ultimate Trip Time Per Pole In Seconds
36.000 minimum all locations and 72.000 maximum all locations
-
Case Material
metal
-
Trip Release Ambient Temp Rating
25.0 deg celsius nominal all locations
-
Frequency In Hertz
60.0 all locations
-
Main Contact Tripping Mechanism Type
trip free
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
15000.0 ac all locations
-
Operating Voltage Type And Rating Per Pole In Volts
250.0 ac all locations
-
Terminal Type And Quantity
8 screw