SM-C-642607-4

Circuit Breakers

CIRCUIT BREAKER

SM-C-642607-4

5925-00-247-8886

5925 - Circuit Breakers

Us Army Communications &

CIRCUIT BREAKER

ACT NOW! SUBMIT A QUICK QUOTE.

Technical Characteristics

  • Body Length

    2.000 inches nominal

  • Fragility Factor

    moderately rugged

  • Pole Quantity

    3

  • Arc Quenching Method

    magnetic blowout

  • Mounting Facility Type And Quantity

    6 threaded hole

  • Operating Voltage Type And Rating Per Pole In Volts

    250.0 ac all locations

  • Circuit Protection Type

    overcurrent all locations

  • Trip Release Characteristic

    time delay all locations

  • Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent

    125.0

  • Ultimate Trip Time Per Pole In Seconds

    10.000 minimum and 105.000 maximum all locations

  • Reset Method

    manual

  • Actuator Function

    trip-reset

  • Actuator Position Designation

    at each pole

  • Nominal Thread Size

    0.138 inches

  • Inclosure Protection Type For Which Designed

    fungus resistant and moisture resistant

  • Frequency In Hertz

    400.0

  • Terminal Type And Quantity

    6 tab, solder lug

  • Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps

    1000.0 ac all locations

  • Trip Release Method

    magnetic-hydraulic all locations

  • Main Contact Tripping Mechanism Type

    trip free

  • Manual Actuator Type And Quantity

    3 toggle

  • External Actuator Linkage Arrangement

    one, two, and three linked

  • Internal Trip Release Configuration

    series trip all locations

  • Trip Delay Time In Seconds Per Rated Continuous Current

    2.000 minimum at 200 pct and 20.000 maximum at 200 pct all locations

  • Thread Series Designator

    unc

  • Thread Pitch Diameters

    +0.1177/+0.1214 inches

  • Body Style

    8c multipole-multiple actuator type

  • Body Width

    2.250 inches nominal

  • Case Material

    plastic

  • Center To Center Distance Between Terminals Parallel To Length

    1.560 inches nominal

  • Center To Center Distance Between Terminals Parallel To Width

    1.500 inches nominal

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Length

    1.660 inches nominal

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Width

    1.500 inches nominal

  • Boss Height

    0.130 inches nominal

  • Mounting Surface To Terminal End Distance

    1.880 inches nominal

  • Storage Type

    general purpose warehouse

  • Thread Quantity Per Inch

    32

  • Maximum Continuous Load Current Rating Per Pole

    3.0 amperes ac all locations

Certified to
AS6081 Methods

Implementing Quality Procurement

A rigorous vendor selection process and vendor management system are essential to ensuring quality.
Read more...

Supplying Quality Products

We take every measure to ensure that we supply quality, authentic parts including a strict vendor selection process and rigorous product inspections..
Read more...

Providing Quality People

Our team of dedicated account managers, procurement professionals and specialized inspectors is the most valuable resource we have.
Read more...