Technical Characteristics
-
Maximum Continuous Load Current Rating Per Pole
125.0 amperes ac all locations and 125.0 amperes dc all locations
-
Overall Height
3.109 inches nominal
-
Frequency In Hertz
60.0 all locations
-
Overall Length
8.469 inches nominal
-
Terminal Type And Quantity
6 screw
-
Overall Width
3.891 inches nominal
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
225.0 all locations
-
Trip Release Ambient Temp Rating
50.0 deg celsius nominal all locations
-
Adjustable Trip Setting Current Range Per Pole In Amps
+750.0/+875.0 ac all locations and +750.0/+875.0 dc all locations
-
Trip Release Method
thermal-magnetic all locations
-
Mounting Facility Type And Quantity
3 terminal
-
Trip Release Characteristic
instantaneous all locations and time delay all locations
-
Trip Delay Time In Seconds Per Rated Continuous Current
150.000 minimum at 300 pct all locations and 420.000 maximum at 300 pct all locations
-
Operating Voltage Type And Rating Per Pole In Volts
500.0 ac all locations and 250.0 dc all locations
-
Features Provided
adjustable trip release
-
Body Style
rectangular dimensional envelope
-
Circuit Protection Type
overcurrent all locations
-
Pole Quantity
3