Technical Characteristics
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
200.0 all locations
-
Pole Quantity
3
-
Circuit Protection Type
overcurrent all locations
-
Actuator Function
trip w/separate reset
-
Reset Method
manual
-
Operating Voltage Type And Rating Per Pole In Volts
500.0 ac all locations and 250.0 dc all locations
-
Maximum Continuous Load Current Rating Per Pole
225.0 amperes ac all locations and 225.0 amperes dc all locations
-
Trip Release Characteristic
instantaneous all locations and time delay all locations
-
Trip Release Method
thermal-magnetic all locations
-
Trip Release Ambient Temp Rating
50.0 deg celsius nominal all locations
-
Manual Actuator Type And Quantity
1 toggle
-
Frequency In Hertz
60.0 all locations
-
Main Contact Tripping Mechanism Type
trip free
-
Mounting Facility Type And Quantity
4 unthreaded hole
-
Trip Delay Time In Seconds Per Rated Continuous Current
5400.000 nominal at 150 pct all locations
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
20000.0 ac all locations and 15000.0 dc all locations
-
Unthreaded Mounting Hole Diameter
0.375 inches nominal
-
Case Material
plastic