Circuit Breakers
CIRCUIT BREAKER
3-8-2C1
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Fragility Factor
moderately rugged
-
Reset Method
manual
-
Actuator Position Designation
at pole one
-
Actuator Function
trip-reset
-
Terminal Type And Quantity
2 screw
-
Circuit Protection Type
overcurrent single location
-
Arc Quenching Method
air
-
Maximum Continuous Load Current Rating Per Pole
15.0 amperes ac single location
-
Pole Quantity
1
-
Case Material
metal
-
Manual Actuator Type And Quantity
1 toggle
-
Storage Type
any acceptable
-
Trip Release Method
thermal-magnetic single location
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
5000.0 ac single location
-
Trip Release Ambient Temp Rating
25.0 deg celsius nominal single location
-
Main Contact Tripping Mechanism Type
trip free
-
Body Width
0.969 inches nominal
-
Body Length
3.750 inches nominal
-
Body Style
single pole type
-
Mounting Facility Type And Quantity
1 slot
-
Cubic Measure
8.176 cubic inches
-
Frequency In Hertz
60.0 single location
-
Body Height
2.250 inches nominal
-
Operating Voltage Type And Rating Per Pole In Volts
120.0 ac single location
-
Trip Delay Time In Seconds Per Rated Continuous Current
24.000 minimum at 200 pct single location and 58.000 maximum at 200 pct single location
-
Trip Release Characteristic
instantaneous single location and time delay single location
-
Boss Height
0.109 inches nominal
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
120.0 single location