Circuit Breakers
CIRCUIT BREAKER
10382637
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Reset Method
manual
-
Actuator Position Designation
at pole one
-
Trip Release Characteristic
time delay all locations
-
Actuator Function
trip-reset
-
Terminal Type And Quantity
4 screw
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
4.500 inches nominal
-
Center To Center Distance Between Terminals Parallel To Width
1.375 inches nominal
-
Maximum Continuous Load Current Rating Per Pole
20.0 amperes ac all locations and 20.0 amperes dc all locations
-
Body Width
2.750 inches nominal
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0 all locations
-
Trip Release Method
thermal-magnetic all locations
-
Boss Height
0.187 inches nominal
-
Body Height
3.500 inches nominal
-
Body Style
multipole-single actuator type
-
Trip Release Ambient Temp Rating
25.0 deg celsius nominal all locations
-
Arc Quenching Method
deion
-
Manual Actuator Type And Quantity
1 toggle
-
Frequency In Hertz
60.0 all locations
-
Main Contact Tripping Mechanism Type
trip free
-
Mounting Facility Type And Quantity
4 unthreaded hole
-
Trip Delay Time In Seconds Per Rated Continuous Current
75.000 nominal at 200 pct all locations and 2600.000 nominal at 125 pct all locations and 24.000 nominal at 300 pct all locations
-
Body Length
6.000 inches nominal
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Width
1.375 inches nominal
-
Center To Center Distance Between Terminals Parallel To Length
5.062 inches nominal
-
Operating Voltage Type And Rating Per Pole In Volts
240.0 ac all locations and 240.0 dc all locations
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
7500.0 ac all locations and 5000.0 dc all locations
-
Case Material
plastic
-
Unthreaded Mounting Hole Diameter
0.187 inches nominal
-
Circuit Protection Type
overcurrent all locations
-
Pole Quantity
2