AM12M6-5-4
Circuit Breakers
CIRCUIT BREAKER
AM12M6-5-4
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Actuator Position Designation
at pole one
-
Reset Method
manual
-
Circuit Protection Type
overcurrent .
-
Operating Voltage Type And Rating Per Pole In Volts
250.0 ac .
-
Mounting Facility Type And Quantity
2 threaded hole
-
Mounting Surface To Terminal End Distance
2.471 inches nominal
-
Boss Height
0.140 inches nominal
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
2.062 inches nominal
-
Case Material
plastic
-
Body Length
2.500 inches nominal
-
Body Style
caaql 12a
-
Terminal Type And Quantity
2 threaded stud
-
Thread Series Designator
unc
-
Frequency In Hertz
60.0
-
Inclosure Protection Type For Which Designed
explosion resistant and fungus resistant and moisture resistant
-
Trip Delay Time In Seconds Per Rated Continuous Current
10.000 minimum at 150 pct and 30.000 maximum at 150 pct and 4.000 minimum at 200 pct and 10.000 maximum at 200 pct and 1.400 minimum at 300 pct and 4.000 maximum at 300 pct .
-
Nominal Thread Size
0.138 inches
-
Internal Trip Release Configuration
series trip .
-
Actuator Function
trip-reset
-
Manual Actuator Type And Quantity
1 toggle
-
Main Contact Tripping Mechanism Type
trip free
-
Ultimate Trip Time Per Pole In Seconds
18.000 minimum and 70.000 maximum .
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0
-
Trip Release Characteristic
time delay .
-
Trip Release Method
magnetic-hydraulic .
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
1000.0 ac .
-
Maximum Continuous Load Current Rating Per Pole
5.0 amperes ac .
-
Thread Quantity Per Inch
32
-
Pole Quantity
1
-
Center To Center Distance Between Terminals Parallel To Length
1.938 inches nominal
-
Body Width