26614
Circuit Breakers
CIRCUIT BREAKER
26614
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Pole Quantity
3
-
Maximum Continuous Load Current Rating Per Pole
35.0 amperes ac all locations and 35.0 amperes dc
-
Operating Voltage Type And Rating Per Pole In Volts
250.0 ac all locations and 250.0 dc
-
Trip Release Characteristic
time delay all locations
-
Main Contact Tripping Mechanism Type
trip free
-
Manual Actuator Type And Quantity
1 toggle
-
Trip Delay Time In Seconds Per Rated Continuous Current
120.000 nominal at 150 pct all locations and 45.000 nominal at 200 pct
-
Arc Quenching Method
deion
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
5000.0 ac all locations and 5000.0 dc
-
Circuit Protection Type
overcurrent all locations
-
Trip Release Method
magnetic all locations
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
112.0 all locations
-
Reset Method
manual
-
Actuator Function
reset
-
Trip Release Ambient Temp Rating
25.0 deg celsius nominal all locations