APL-11-1-62-302-M

Circuit Breakers

CIRCUIT BREAKER

APL-11-1-62-302-M

5925-00-318-0026

5925 - Circuit Breakers

Sensata Technologies Maryland Inc

CIRCUIT BREAKER

ACT NOW! SUBMIT A QUICK QUOTE.

Technical Characteristics

  • Fragility Factor

    moderately rugged

  • Center To Center Distance Between Terminals Parallel To Width

    0.750 inches nominal

  • Center To Center Distance Between Terminals Parallel To Length

    1.660 inches minimum and 1.960 inches maximum

  • Special Handling Feature

    magnetic

  • Circuit Protection Type

    overcurrent all locations

  • Pole Quantity

    2

  • Thread Series Designator

    unc

  • Actuator Position Designation

    at each pole

  • Reset Method

    manual

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Length

    2.046 inches minimum and 2.078 inches maximum

  • Storage Type

    general purpose warehouse

  • ~1

    data on certain environmental and performanc

  • Case Material

    plastic

  • External Actuator Linkage Arrangement

    one and two linked

  • Body Width

    1.500 inches nominal

  • Trip Delay Time In Seconds Per Rated Continuous Current

    2.200 minimum at 200 pct all locations and 20.000 maximum at 200 pct all locations

  • Terminal Type And Quantity

    4 threaded stud

  • Body Length

    2.510 inches maximum

  • Thread Pitch Diameters

    +0.1177/+0.1214 inches

  • Inclosure Protection Type For Which Designed

    moisture resistant and salt spray proof and fungus resistant and shock resistant and vibration resistant

  • Manual Actuator Type And Quantity

    2 toggle

  • Specification/Standard Data

    81349-mil-c-55629/3 government specification

  • Boss Height

    0.140 inches nominal

  • Arc Quenching Method

    magnetic blowout

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Width

    0.750 inches nominal

  • Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent

    115.0 all locations

  • Main Contact Tripping Mechanism Type

    trip free

  • Frequency In Hertz

    60.0 all locations

  • Nominal Thread Size

    0.138 inches

  • Mounting Surface To Terminal End Distance

    2.553 inches maximum

  • Maximum Continuous Load Current Rating Per Pole

    3.0 amperes ac all locations

  • Body Style

    multipole-multiple actuator type

  • Trip Release Method

    magnetic all locations

  • Operating Voltage Type And Rating Per Pole In Volts

    240.0 ac all locations

  • Thread Quantity Per Inch

    32

  • Mounting Facility Type And Quantity

    4 threaded hole

  • Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps

    1000.0 ac all locations

  • Internal Trip Release Configuration

    series trip all locations

  • Actuator Function

    trip-reset

  • Trip Release Characteristic

    time delay all locations

  • Test Data Document

    81349-mil-c-55629 specification (includes engineering type bulletins, brochures,etc., that reflect specification type data in specification format; excludes commercial catalogs, industry directories, and similar trade publications, reflecting general type

Certified to
AS6081 Methods

Implementing Quality Procurement

A rigorous vendor selection process and vendor management system are essential to ensuring quality.
Read more...

Supplying Quality Products

We take every measure to ensure that we supply quality, authentic parts including a strict vendor selection process and rigorous product inspections..
Read more...

Providing Quality People

Our team of dedicated account managers, procurement professionals and specialized inspectors is the most valuable resource we have.
Read more...