68E3334

Circuit Breakers

CIRCUIT BREAKER

68E3334

5925-00-345-7746

5925 - Circuit Breakers

Eaton Corporation

CIRCUIT BREAKER

ACT NOW! SUBMIT A QUICK QUOTE.

Technical Characteristics

  • Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent

    125.0 all locations

  • Trip Release Method

    thermal-magnetic all locations

  • Body Width

    9.000 inches nominal

  • Actuator Position Designation

    at pole two

  • Trip Release Ambient Temp Rating

    50.0 deg celsius nominal all locations

  • Inclosure Protection Type For Which Designed

    fungus resistant and moisture resistant

  • Body Style

    multipole-single actuator type

  • Manual Actuator Type And Quantity

    1 toggle

  • Thread Quantity Per Inch

    20

  • Frequency In Hertz

    60.0 all locations

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Length

    9.875 inches nominal

  • Trip Release Characteristic

    instantaneous all locations

  • Pole Quantity

    3

  • Circuit Protection Type

    overcurrent all locations

  • Thread Series Designator

    unc

  • Reset Method

    manual

  • Operating Voltage Type And Rating Per Pole In Volts

    500.0 ac all locations and 250.0 dc all locations

  • Center To Center Distance Between Terminals Parallel To Length

    9.875 inches nominal

  • Actuator Function

    trip-reset

  • Center To Center Distance Between Terminals Parallel To Width

    3.000 inches nominal

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Width

    3.000 inches nominal

  • Main Contact Tripping Mechanism Type

    trip free

  • Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps

    20000.0 ac all locations and 15000.0 dc all locations

  • Body Length

    11.000 inches nominal

  • Boss Height

    0.312 inches nominal

  • Mounting Facility Type And Quantity

    4 threaded stud

  • Nominal Thread Size

    0.250 inches

  • Maximum Continuous Load Current Rating Per Pole

    250.0 amperes ac all locations and 250.0 amperes dc all locations

  • Body Height

    4.562 inches nominal

  • Case Material

    plastic

  • Terminal Type And Quantity

    6 threaded stud

Certified to
AS6081 Methods

Implementing Quality Procurement

A rigorous vendor selection process and vendor management system are essential to ensuring quality.
Read more...

Supplying Quality Products

We take every measure to ensure that we supply quality, authentic parts including a strict vendor selection process and rigorous product inspections..
Read more...

Providing Quality People

Our team of dedicated account managers, procurement professionals and specialized inspectors is the most valuable resource we have.
Read more...