S1299961
Circuit Breakers
CIRCUIT BREAKER
S1299961
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
8.750 inches nominal
-
Operating Voltage Type And Rating Per Pole In Volts
250.0 dc all locations
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Width
1.625 inches nominal
-
Terminal Type And Quantity
4 threaded stud
-
Case Material
plastic
-
Mounting Facility Type And Quantity
4 unthreaded hole
-
Main Contact Tripping Mechanism Type
trip free
-
Manual Actuator Type And Quantity
1 toggle
-
Arc Quenching Method
deion
-
Actuator Function
reset
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
200.0 all locations
-
Overall Height
4.750 inches nominal
-
Circuit Protection Type
overcurrent all locations
-
Pole Quantity
2
-
Reset Method
manual
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
10000.0 dc all locations
-
Trip Release Ambient Temp Rating
50.0 deg celsius nominal all locations
-
Maximum Continuous Load Current Rating Per Pole
50.0 amperes dc all locations
-
Unthreaded Mounting Hole Diameter
0.281 inches nominal
-
Trip Release Method
magnetic all locations
-
Overall Width
5.000 inches nominal
-
Trip Release Characteristic
instantaneous all locations and time delay all locations
-
Overall Length
10.000 inches nominal
-
Trip Delay Time In Seconds Per Rated Continuous Current
240.000 maximum at 200 pct all locations and 10.000 minimum at 200 pct all locations and 2.000 minimum at 300 pct all locations and 7.500 maximum at 300 pct all locations