APL111-559-460

Circuit Breakers

CIRCUIT BREAKER

APL111-559-460

5925-00-403-4061

5925 - Circuit Breakers

Sensata Technologies Maryland Inc

CIRCUIT BREAKER

ACT NOW! SUBMIT A QUICK QUOTE.

Technical Characteristics

  • Fragility Factor

    moderately rugged

  • Switch Terminal Type

    tab, solder lug

  • Center To Center Distance Between Terminals Parallel To Width

    0.750 inches nominal

  • Special Handling Feature

    magnetic

  • Pole Quantity

    3

  • Circuit Protection Type

    overcurrent all locations

  • Thread Series Designator

    unc

  • Actuator Position Designation

    at each pole

  • Reset Method

    manual

  • Trip Delay Time In Seconds Per Rated Continuous Current

    20.000 minimum at 200 pct all locations and 70.000 maximum at 200 pct all locations

  • Storage Type

    general purpose warehouse

  • Trip Release Characteristic

    time delay all locations

  • Actuator Function

    trip-reset

  • External Actuator Linkage Arrangement

    one, two, and three linked

  • Internal Trip Release Configuration

    series trip all locations

  • Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps

    1000.0 ac all locations

  • Thread Quantity Per Inch

    32

  • Mounting Surface To Terminal End Distance

    2.611 inches nominal

  • Trip Release Method

    magnetic all locations

  • Body Style

    multipole-multiple actuator type

  • Inclosure Protection Type For Which Designed

    fungus resistant and shock resistant and humidity resistant and moisture resistant and salt spray proof

  • Switch Contact Arrangement

    single pole, double throw

  • Switch Current Rating And Type In Amps

    2.5 ac and 1.0 dc

  • Switch Voltage Rating And Type In Volts

    250.0 ac and 50.0 dc

  • Mounting Facility Type And Quantity

    6 threaded hole

  • Nominal Thread Size

    0.138 inches

  • Body Width

    2.250 inches nominal

  • Main Contact Tripping Mechanism Type

    trip free

  • Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent

    115.0 all locations

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Width

    0.750 inches nominal

  • Arc Quenching Method

    magnetic blowout

  • Body Length

    2.500 inches nominal

  • Boss Height

    0.140 inches nominal

  • Unpackaged Unit Weight

    14.250 ounces

  • Test Data Document

    13499-260-4015 drawing (this is the basic governing drawing, such as a contractor drawing, original equipment manufacturer drawing, etc.; excludes any specification, standard or other document that may be referenced in a basic governing drawing)

  • Maximum Continuous Load Current Rating Per Pole

    15.0 amperes ac all locations

  • Operating Voltage Type And Rating Per Pole In Volts

    250.0 ac all locations

  • Frequency In Hertz

    400.0 all locations

  • Thread Pitch Diameters

    +0.1177/+0.1214 inches

  • Auxiliary Switch Function And Quantity

    1 alarm

  • Manual Actuator Type And Quantity

    3 toggle

  • Switch Location And Position Designation

    internal at pole one

  • Case Material

    plastic

  • Center To Center Distance Between Terminals Parallel To Length

    1.938 inches nominal

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Length

    2.062 inches nominal

  • Terminal Type And Quantity

    6 threaded stud

Certified to
AS6081 Methods

Implementing Quality Procurement

A rigorous vendor selection process and vendor management system are essential to ensuring quality.
Read more...

Supplying Quality Products

We take every measure to ensure that we supply quality, authentic parts including a strict vendor selection process and rigorous product inspections..
Read more...

Providing Quality People

Our team of dedicated account managers, procurement professionals and specialized inspectors is the most valuable resource we have.
Read more...