2XAM1516-20-250VAC60C1
Circuit Breakers
CIRCUIT BREAKER
2XAM1516-20-250VAC60C1
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Body Length
3.730 inches nominal
-
Body Width
2.030 inches nominal
-
Case Material
plastic
-
Center To Center Distance Between Terminals Parallel To Length
3.060 inches nominal
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
2.750 inches nominal
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Width
1.030 inches nominal
-
Boss Height
0.160 inches nominal
-
Mounting Surface To Terminal End Distance
3.250 inches nominal
-
Pole Quantity
2
-
Mounting Facility Type And Quantity
4 threaded hole
-
Storage Type
general purpose warehouse
-
Thread Quantity Per Inch
32
-
Maximum Continuous Load Current Rating Per Pole
20.0 amperes ac
-
Main Contact Tripping Mechanism Type
trip free
-
Manual Actuator Type And Quantity
2 toggle
-
Internal Trip Release Configuration
series trip
-
Nominal Thread Size
0.138 inches
-
Frequency In Hertz
60.0
-
Unpackaged Unit Weight
1.200 pounds
-
Thread Series Designator
unc
-
Center To Center Distance Between Terminals Parallel To Width
1.000 inches nominal
-
Arc Quenching Method
magnetic blowout
-
Operating Voltage Type And Rating Per Pole In Volts
250.0 ac
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
1500.0 ac
-
Circuit Protection Type
overcurrent
-
Trip Release Method
magnetic-hydraulic
-
Trip Release Characteristic
time delay
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0
-
Reset Method
manual
-
Actuator Function
trip-reset
-
Actuator Position Designation
at each pole
-
External Actuator Linkage Arrangement
one and two linked
-
Trip Delay Time In Seconds Per Rated Continuous Current
35.000 minimum at 200 pct and 130.000 maximum at 200 pct
-
Inclosure Protection Type For Which Designed
shock resistant and vibration resistant
-
Terminal Type And Quantity
4 threaded stud