SM333-2-60-2

Circuit Breakers

CIRCUIT BREAKER

SM333-2-60-2

5925-00-421-2803

5925 - Circuit Breakers

Eaton Corp

CIRCUIT BREAKER

ACT NOW! SUBMIT A QUICK QUOTE.

Technical Characteristics

  • Actuator Function

    trip-reset

  • Actuator Position Designation

    at pole two

  • Inclosure Protection Type For Which Designed

    fungus resistant and hermetically sealed

  • Frequency In Hertz

    60.0 all locations

  • Definitive Government Spec/Std Reference

    m39019/05-83

  • Manufacturers Code

    81349

  • Test Data Document

    81349-mil-c-39019 specification

  • Thread Pitch Diameters

    0.3503 to 0.3537 inches

  • Body Style

    1b multipole-single actuator type

  • Bushing Length

    0.365 inches minimum and 0.385 inches maximum

  • Body Width

    1.844 inches minimum and 1.906 inches maximum

  • Center To Center Distance Between Terminals Parallel To Length

    0.865 inches minimum and 0.885 inches maximum

  • Center To Center Distance Between Terminals Parallel To Width

    0.615 inches minimum and 0.635 inches maximum

  • Pole Quantity

    3

  • Thread Quantity Per Inch

    32

  • Operating Voltage Type And Rating Per Pole In Volts

    240.0 ac all locations

  • Circuit Protection Type

    overcurrent all locations

  • Trip Release Characteristic

    time delay all locations

  • Ultimate Trip Time Per Pole In Seconds

    0.200 minimum and 7.000 maximum all locations

  • Reset Method

    manual

  • Manual Actuator Type And Quantity

    1 toggle

  • Body Length

    1.552 inches minimum and 1.572 inches maximum

  • Case Material

    metal

  • Mounting Surface To Terminal End Distance

    1.690 inches minimum and 1.710 inches maximum

  • Iii Arc Quenching Method

    magnetic blowout

  • Mounting Facility Type And Quantity

    1 threaded bushing w/panel seal

  • Iii Storage Type

    general purpose warehouse

  • Maximum Continuous Load Current Rating Per Pole

    2.0 amperes ac all locations

  • Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps

    300.0 ac all locations

  • Trip Release Method

    magnetic all locations

  • Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent

    115.0 all locations

  • Main Contact Tripping Mechanism Type

    trip free

  • Internal Trip Release Configuration

    series trip all locations

  • Nominal Thread Size

    0.375 inches

  • Trip Delay Time In Seconds Per Rated Continuous Current

    0.055 minimum at 200 pct and 0.950 maximum at 200 pct and 0.240 maximum at 400 pct all locations

  • Non-Definitive Government Spec/Std Reference

    mil-c-39019/5

  • Thread Series Designator

    unef

  • Terminal Type And Quantity

    6 wire hook

  • Specification/Standard Data

    81349-mil-c-39019/5 government specification

Certified to
AS6081 Methods

Implementing Quality Procurement

A rigorous vendor selection process and vendor management system are essential to ensuring quality.
Read more...

Supplying Quality Products

We take every measure to ensure that we supply quality, authentic parts including a strict vendor selection process and rigorous product inspections..
Read more...

Providing Quality People

Our team of dedicated account managers, procurement professionals and specialized inspectors is the most valuable resource we have.
Read more...