4975D71G34
Circuit Breakers
CIRCUIT BREAKER
4975D71G34
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Terminal Type And Quantity
6 compression
-
Main Contact Tripping Mechanism Type
trip free
-
Mounting Facility Type And Quantity
4 unthreaded hole
-
Trip Delay Time In Seconds Per Rated Continuous Current
28.000 minimum at 200 pct all locations and 73.000 maximum at 200 pct all locations
-
Inclosure Protection Type For Which Designed
general purpose
-
Boss Height
0.219 inches nominal
-
Maximum Continuous Load Current Rating Per Pole
15.0 amperes ac all locations
-
Unthreaded Mounting Hole Diameter
0.375 inches nominal
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Width
1.375 inches nominal
-
Frequency In Hertz
400.0 all locations
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
7.500 inches nominal
-
Operating Voltage Type And Rating Per Pole In Volts
600.0 ac all locations
-
Case Material
plastic
-
Body Height
3.812 inches nominal
-
Pole Quantity
3
-
Circuit Protection Type
overcurrent all locations
-
Body Width
4.125 inches nominal
-
Reset Method
manual
-
Storage Type
general purpose warehouse
-
Trip Release Ambient Temp Rating
40.0 deg celsius nominal all locations
-
Actuator Function
trip-reset
-
Body Length
9.375 inches nominal
-
Trip Release Characteristic
instantaneous all locations and time delay all locations
-
Center To Center Distance Between Terminals Parallel To Length
7.875 inches nominal
-
Center To Center Distance Between Terminals Parallel To Width
1.375 inches nominal
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0 all locations
-
Trip Release Method
thermal-magnetic all locations
-
Actuator Position Designation
at pole two
-
Body Style
multipole-single actuator type
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
20000.0 ac all locations
-
Manual Actuator Type And Quantity
1 toggle