BA2030
Circuit Breakers
CIRCUIT BREAKER
BA2030
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Trip Delay Time In Seconds Per Rated Continuous Current
70.000 minimum at 200 pct all locations and 85.000 maximum at 200 pct all locations
-
Operating Voltage Type And Rating Per Pole In Volts
120.0 ac all locations
-
Terminal Type And Quantity
2 screw and 2 tab, solder lug
-
Case Material
plastic
-
Trip Release Ambient Temp Rating
40.0 deg celsius maximum all locations
-
Maximum Continuous Load Current Rating Per Pole
30.0 amperes ac all locations
-
Mounting Facility Type And Quantity
4 terminal
-
Circuit Protection Type
overcurrent all locations
-
Pole Quantity
2
-
Reset Method
manual
-
Actuator Position Designation
at pole one
-
Trip Release Characteristic
time delay all locations
-
Actuator Function
trip-reset
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0 all locations
-
Trip Release Method
thermal-magnetic all locations
-
Boss Height
0.187 inches nominal
-
Body Width
2.000 inches maximum
-
Body Height
2.375 inches nominal
-
Body Style
multipole-single actuator type
-
Center To Center Distance Between Terminals Parallel To Width
1.000 inches nominal
-
Body Length
3.000 inches nominal
-
Manual Actuator Type And Quantity
1 toggle
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
10000.0 ac all locations
-
Frequency In Hertz
60.0 all locations
-
Main Contact Tripping Mechanism Type
trip free