79-106-7
Circuit Breakers
CIRCUIT BREAKER
79-106-7
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Center To Center Distance Between Terminals Parallel To Length
1.938 inches nominal
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
2.062 inches nominal
-
Terminal Type And Quantity
6 threaded stud
-
Fragility Factor
moderately rugged
-
Center To Center Distance Between Terminals Parallel To Width
0.750 inches nominal
-
Special Handling Feature
magnetic
-
Pole Quantity
3
-
Circuit Protection Type
overcurrent all locations
-
Thread Series Designator
unc
-
Actuator Position Designation
at each pole
-
Reset Method
manual
-
Trip Delay Time In Seconds Per Rated Continuous Current
0.130 minimum at 200 pct all locations and 0.700 maximum at 200 pct all locations
-
Storage Type
general purpose warehouse
-
Trip Release Characteristic
time delay all locations
-
Actuator Function
trip-reset
-
Inclosure Protection Type For Which Designed
explosion resistant
-
External Actuator Linkage Arrangement
one, two, and three linked
-
Maximum Continuous Load Current Rating Per Pole
9.0 amperes ac all locations
-
Internal Trip Release Configuration
series trip all locations
-
Thread Quantity Per Inch
32
-
Operating Voltage Type And Rating Per Pole In Volts
240.0 ac all locations
-
Trip Release Method
magnetic-hydraulic all locations
-
Body Style
multipole-multiple actuator type
-
Mounting Facility Type And Quantity
6 threaded hole
-
Nominal Thread Size
0.138 inches
-
Frequency In Hertz
60.0 all locations
-
Body Width
2.250 inches nominal
-
Mounting Surface To Terminal End Distance
2.471 inches nominal
-
Main Contact Tripping Mechanism Type
trip free
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
115.0 all locations
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Width
0.750 inches nominal
-
Arc Quenching Method
magnetic blowout
-
Body Length
2.500 inches nominal
-
Boss Height
0.140 inches nominal
-
Ultimate Trip Time Per Pole In Seconds
0.400 minimum all locations and 2.000 maximum all locations
-
Thread Pitch Diameters
+0.1177/+0.1214 inches
-
Manual Actuator Type And Quantity
3 toggle
-
Test Data Document
06481-900486 drawing (this is the basic governing drawing, such as a contractor drawing, original equipment manufacturer drawing, etc.; excludes any specification, standard or other document that may be referenced in a basic governing drawing)
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
300.0 ac all locations
-
Case Material
plastic