Technical Characteristics

  • Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps

    1000.0 ac single location and 2000.0 dc single location

  • Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent

    135.0 single location

  • Mounting Surface To Terminal End Distance

    2.035 inches nominal

  • Pole Quantity

    1

  • Internal Trip Release Configuration

    series trip single location

  • Body Width

    0.690 inches nominal

  • Trip Release Characteristic

    time delay single location

  • Reset Method

    manual

  • Actuator Position Designation

    at pole one

  • Storage Type

    general purpose warehouse

  • Actuator Function

    trip-reset

  • Inclosure Protection Type For Which Designed

    vibrationproof

  • Nominal Thread Size

    0.375 inches

  • Circuit Protection Type

    overcurrent single location

  • Trip Release Method

    thermal single location

  • Mounting Facility Type And Quantity

    1 threaded bushing

  • Body Length

    1.375 inches nominal

  • Manual Actuator Type And Quantity

    1 push-pull

  • Trip Release Ambient Temp Rating

    25.0 deg celsius nominal single location

  • Main Contact Tripping Mechanism Type

    trip free

  • Bushing Length

    0.375 inches nominal

  • Operating Voltage Type And Rating Per Pole In Volts

    125.0 ac single location and 50.0 dc single location

  • Thread Quantity Per Inch

    24

  • Trip Delay Time In Seconds Per Rated Continuous Current

    7.500 minimum at 200 pct single location and 20.000 maximum at 200 pct single location

  • Body Style

    single pole type

  • Maximum Continuous Load Current Rating Per Pole

    10.0 amperes ac single location and 10.0 amperes dc single location

  • Frequency In Hertz

    60.0 single location

  • Terminal Type And Quantity

    2 tab w/screw

  • Thread Series Designator

    un

  • Unpackaged Unit Weight

    2.000 ounces

  • Center To Center Distance Between Terminals Parallel To Length

    1.020 inches nominal

  • Case Material

    plastic

Certified to
AS6081 Methods

Implementing Quality Procurement

A rigorous vendor selection process and vendor management system are essential to ensuring quality.
Read more...

Supplying Quality Products

We take every measure to ensure that we supply quality, authentic parts including a strict vendor selection process and rigorous product inspections..
Read more...

Providing Quality People

Our team of dedicated account managers, procurement professionals and specialized inspectors is the most valuable resource we have.
Read more...