M39019-6-59

Circuit Breakers

CIRCUIT BREAKER

M39019-6-59

5925-00-460-5653

5925 - Circuit Breakers

Military Specifications

CIRCUIT BREAKER

ACT NOW! SUBMIT A QUICK QUOTE.

Technical Characteristics

  • Pole Quantity

    3

  • Mounting Facility Type And Quantity

    1 threaded bushing w/panel seal

  • Storage Type

    general purpose warehouse

  • Thread Quantity Per Inch

    32

  • Operating Voltage Type And Rating Per Pole In Volts

    240.0 ac all locations

  • Trip Release Method

    magnetic all locations

  • Trip Release Characteristic

    time delay all locations

  • Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent

    125.0

  • Main Contact Tripping Mechanism Type

    trip free

  • Manual Actuator Type And Quantity

    1 toggle

  • Actuator Function

    trip-reset

  • Internal Trip Release Configuration

    series trip all locations

  • Nominal Thread Size

    0.375 inches

  • Switch Location And Position Designation

    internal at pole three

  • Trip Delay Time In Seconds Per Rated Continuous Current

    0.055 minimum at 200 pct and 0.950 maximum at 200 pct and 0.240 maximum at 400 pct all locations

  • Inclosure Protection Type For Which Designed

    fungus resistant

  • Switch Voltage Rating And Type In Volts

    120.0 ac and 50.0 dc

  • Frequency In Hertz

    400.0

  • Body Style

    1b multipole-single actuator type

  • Body Length

    1.937 inches maximum

  • Center To Center Distance Between Terminals Parallel To Length

    0.906 inches maximum

  • Switch Contact Arrangement

    single pole, double throw

  • Mounting Surface To Terminal End Distance

    any acceptable

  • Maximum Continuous Load Current Rating Per Pole

    10.0 amperes ac all locations

  • Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps

    300.0 ac all locations

  • Circuit Protection Type

    overcurrent all locations

  • Ultimate Trip Time Per Pole In Seconds

    0.200 minimum and 7.000 maximum all locations

  • Reset Method

    manual

  • Actuator Position Designation

    at pole two

  • Auxiliary Switch Function And Quantity

    1 alarm

  • Switch Terminal Type

    tab, solder lug

  • Switch Current Rating And Type In Amps

    0.5 ac and 0.5 dc

  • Bushing Length

    0.280 inches minimum and 0.380 inches maximum

  • Body Width

    1.562 inches maximum

  • Case Material

    metal

  • Center To Center Distance Between Terminals Parallel To Width

    0.625 inches nominal

  • Test Data Document

    81349-mil-c-39019 specification

  • Thread Series Designator

    unef

  • Terminal Type And Quantity

    6 wire hook

Certified to
AS6081 Methods

Implementing Quality Procurement

A rigorous vendor selection process and vendor management system are essential to ensuring quality.