CJ3-G3-U-200-9

Circuit Breakers

CIRCUIT BREAKER

CJ3-G3-U-200-9

5925-00-460-5711

5925 - Circuit Breakers

Eaton Corp

CIRCUIT BREAKER

ACT NOW! SUBMIT A QUICK QUOTE.

Technical Characteristics

  • Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps

    10000.0 ac all locations

  • Frequency In Hertz

    60.0 all locations

  • Terminal Type And Quantity

    6 compression

  • Main Contact Tripping Mechanism Type

    trip free

  • Mounting Facility Type And Quantity

    4 unthreaded hole

  • Arc Quenching Method

    magnetic blowout

  • Boss Height

    0.218 inches nominal

  • Body Length

    7.000 inches nominal

  • Inclosure Protection Type For Which Designed

    general purpose

  • Maximum Continuous Load Current Rating Per Pole

    200.0 amperes ac all locations

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Width

    1.500 inches nominal

  • Case Material

    plastic

  • Fragility Factor

    moderately rugged

  • Special Handling Feature

    magnetic

  • Pole Quantity

    3

  • Circuit Protection Type

    overcurrent all locations

  • Reset Method

    manual

  • Center To Center Distance Between Terminals Parallel To Width

    1.500 inches nominal

  • Storage Type

    general purpose warehouse

  • Trip Release Characteristic

    time delay all locations

  • Actuator Function

    trip-reset

  • Body Width

    4.500 inches nominal

  • Internal Trip Release Configuration

    series trip all locations

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Length

    4.359 inches nominal

  • Operating Voltage Type And Rating Per Pole In Volts

    240.0 ac all locations

  • Trip Release Method

    magnetic-hydraulic all locations

  • Body Height

    2.906 inches nominal

  • Unthreaded Mounting Hole Diameter

    0.250 inches nominal

  • Trip Delay Time In Seconds Per Rated Continuous Current

    11.500 minimum at 200 pct all locations and 99.000 maximum at 200 pct all locations

  • Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent

    125.0 all locations

  • Actuator Position Designation

    at pole two

  • Unpackaged Unit Weight

    4.500 pounds

  • Body Style

    multipole-single actuator type

  • Center To Center Distance Between Terminals Parallel To Length

    6.125 inches nominal

  • Manual Actuator Type And Quantity

    1 toggle

Certified to
AS6081 Methods

Implementing Quality Procurement

A rigorous vendor selection process and vendor management system are essential to ensuring quality.
Read more...

Supplying Quality Products

We take every measure to ensure that we supply quality, authentic parts including a strict vendor selection process and rigorous product inspections..
Read more...

Providing Quality People

Our team of dedicated account managers, procurement professionals and specialized inspectors is the most valuable resource we have.
Read more...