171-105-9MG6

Circuit Breakers

CIRCUIT BREAKER

171-105-9MG6

5925-00-461-9236

5925 - Circuit Breakers

Eaton Corp

CIRCUIT BREAKER

ACT NOW! SUBMIT A QUICK QUOTE.

Technical Characteristics

  • Body Style

    multipole-multiple actuator type

  • Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent

    125.0 all locations

  • Switch Contact Arrangement

    single pole, double throw

  • Switch Current Rating And Type In Amps

    2.5 ac and 1.0 dc

  • Inclosure Protection Type For Which Designed

    fungus resistant and moisture resistant

  • Switch Voltage Rating And Type In Volts

    250.0 ac and 50.0 dc

  • Operating Voltage Type And Rating Per Pole In Volts

    50.0 dc first location

  • External Actuator Linkage Arrangement

    one, two, three, four, and five linked

  • Nominal Thread Size

    0.138 inches

  • Trip Delay Time In Seconds Per Rated Continuous Current

    0.180 minimum at 200 pct all locations and 0.550 maximum at 200 pct all locations

  • Operating Voltage Type And Rating Per Pole In Volts

    50.0 dc fourth location

  • Main Contact Tripping Mechanism Type

    trip free

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Width

    0.750 inches nominal

  • Body Length

    2.500 inches nominal

  • Operating Voltage Type And Rating Per Pole In Volts

    50.0 dc second location

  • Boss Height

    0.140 inches nominal

  • Maximum Continuous Load Current Rating Per Pole

    7.0 amperes dc fourth location

  • Maximum Continuous Load Current Rating Per Pole

    9.0 amperes dc second location

  • Pole Quantity

    5

  • Maximum Continuous Load Current Rating Per Pole

    7.0 amperes dc third location

  • Body Width

    3.797 inches maximum

  • Operating Voltage Type And Rating Per Pole In Volts

    50.0 dc third location

  • Manual Actuator Type And Quantity

    5 toggle

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Length

    2.060 inches nominal

  • Maximum Continuous Load Current Rating Per Pole

    6.0 amperes dc first location

  • Case Material

    plastic

  • Switch Terminal Type

    tab, solder lug

  • Center To Center Distance Between Terminals Parallel To Width

    0.750 inches nominal

  • Circuit Protection Type

    overcurrent all locations

  • Terminal Type And Quantity

    10 threaded stud

  • Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps

    2000.0 dc all locations

  • Thread Series Designator

    unc

  • Actuator Position Designation

    at each pole

  • Reset Method

    manual

  • Operating Voltage Type And Rating Per Pole In Volts

    40.0 dc fifth location

  • Storage Type

    general purpose warehouse

  • Trip Release Characteristic

    time delay all locations

  • Actuator Function

    trip-reset

  • Internal Trip Release Configuration

    series trip all locations

  • Center To Center Distance Between Terminals Parallel To Length

    1.940 inches nominal

  • Mounting Surface To Terminal End Distance

    2.841 inches nominal

  • Auxiliary Switch Function And Quantity

    4 alarm

  • Thread Quantity Per Inch

    32

  • Mounting Facility Type And Quantity

    10 threaded hole

  • Trip Release Method

    magnetic-hydraulic all locations

  • Maximum Continuous Load Current Rating Per Pole

    11.0 amperes dc fifth location

Certified to
AS6081 Methods

Implementing Quality Procurement

A rigorous vendor selection process and vendor management system are essential to ensuring quality.
Read more...

Supplying Quality Products

We take every measure to ensure that we supply quality, authentic parts including a strict vendor selection process and rigorous product inspections..
Read more...

Providing Quality People

Our team of dedicated account managers, procurement professionals and specialized inspectors is the most valuable resource we have.
Read more...