7360536
Circuit Breakers
CIRCUIT BREAKER
7360536
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Body Style
18a single pole type
-
Body Width
2.125 inches nominal
-
Case Material
plastic
-
Center To Center Distance Between Terminals Parallel To Length
1.500 inches nominal
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
3.500 inches nominal
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Width
1.000 inches nominal
-
Mounting Surface To Terminal End Distance
2.219 inches nominal
-
Mounting Facility Type And Quantity
4 threaded hole
-
Maximum Continuous Load Current Rating Per Pole
175.0 amperes dc single location
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
3000.0 dc single location
-
Trip Release Method
thermal single location
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
130.0 single location
-
Actuator Function
trip-reset
-
Internal Trip Release Configuration
series trip single location
-
Trip Release Ambient Temp Rating
77.0 deg fahrenheit nominal single location
-
Overall Length
4.000 inches nominal
-
Fragility Factor
moderately rugged
-
Pole Quantity
1
-
Storage Type
general purpose warehouse
-
Thread Quantity Per Inch
32
-
Operating Voltage Type And Rating Per Pole In Volts
30.0 dc single location
-
Circuit Protection Type
overcurrent single location
-
Trip Release Characteristic
time delay single location
-
Reset Method
automatic
-
Manual Actuator Type And Quantity
1 toggle
-
Actuator Position Designation
at pole one
-
Nominal Thread Size
0.190 inches
-
Trip Delay Time In Seconds Per Rated Continuous Current
2.700 minimum at 200 pct single location and 6.000 maximum at 200 pct
-
Thread Series Designator
unf
-
Terminal Type And Quantity
2 threaded stud